Installing HiPath 3550, HiPath 3350, HiPath 3500, and HiPath 3300
4.2.4.6
Grounding the System
Implementation guidelines in accordance with IEC 60364 and IEC 60950-1 must be adhered
to during installation.
Grounding: Inspection and Implementation
Preliminary Inspection of the 19-Inch Cabinet:
Is the 19-inch cabinet grounded
by a separate ground conduc-
tor (green/yellow)?
The 19-inch cabinet must be grounded by a sepa-
rate ground conductor (green/yellow).
Danger
If your personnel are not qualified to work on the
low-voltage network (230 Vac), you must hire a li-
censed electrician to install the ground. The
Section 1.6.1, “Connection to the Power Circuit” is
to be adhered to.
Does the 19-inch cabinet have
a potential equalization bus
at which the HiPath 3500 or Hi-
Path 3300 can be grounded?
A potential equalization bus must be installed in
the 19-inch cabinet and connected to the ground
conductor.
Danger
If your personnel are not qualified to work on the
low-voltage network (230 Vac), you must hire a li-
censed electrician to install the ground. The
Section 1.6.1, “Connection to the Power Circuit” is
to be adhered to.
If you answer “Yes” to both questions, the HiPath 3500 or HiPath 3300 systems may be
grounded as described below.
NO
YES
NO
YES