Installing HiPath 3000
Nur für den internen Gebrauch
A31003-H3590-S100-7-7620, 06/2012
4-20
HiPath 3000/5000 V9, Service documentation
inst_h3.fm
Installing HiPath 3800
4.1.4
Installing HiPath 3800 (19-Inch Cabinet)
This section contains information on how to install the HiPath 3800 communication system in
a 19-inch cabinet. This chapter describes the standard installation procedures for the basic sys-
tem. Refer to Chapter 9 for information about supplementary equipment or expansions.
4.1.4.1
Selecting the Installation Site
The installation site is generally determined by the 19-inch cabinet already installed.
The following specifications must be observed when selecting a location:
●
The 19-inch cabinets provided for installing the HiPath 3800 components must have the
following characteristics:
–
Components installed in the 19-inch cabinet must be accessible from both the front
and the rear.
–
It should be possible to install 19-inch components both at the front and at the rear (
four vertical bars).
–
It is recommended that the width of the cabinet measure 700 to 800 mm; the depth at
least 600 mm. Deeper cabinets (800 - 900 mm) make installation, cable servicing, and
the installation of additional components in the rear of the cabinet much easier.
–
The support brackets required for installing the system cabinets must have a minimum
ultimate load of 40 kg. The support brackets must be purchased from the relevant 19-
inch cabinet supplier.
–
The system cabinets must be fixed to the cabinet bars using the angle brackets includ-
ed in the delivery.
●
One height unit (one height unit is approx. 1.7” = 43 mm) must be kept clear above the cab-
inet to accommodate the gray plastic cover (Figure 4-9) attached to the top of the system
cabinets. Never remove this plastic cover.
●
The following minimum clearance must be provided in order to ensure adequate ventilation
of the system cabinets in the 19-inch cabinet (see Figure 4-10):
–
three height units between two stacked system cabinets.
–
one height unit above one system cabinet if a patch panel is being installed, for exam-
ple.
●
To guarantee sufficient heat dissipation, the basic cabinet must be mounted at the lowest
position in a 19-inch cabinet. In a 19-inch cabinet with active (heat-emitting) components
already installed, the lowest position must be cleared for installation of the basic cabinet.
If inactive components (e.g. patch panel) are involved, the basic cabinet can also be in-
stalled above them.