Siemens HI921 Installation Instructions Download Page 2

DETECTOR TESTING

Only qualified service personnel should test. To assure proper
operation of the detector and control panel, the Functional Test
should be conducted. The minimum test schedule may be found
in the current edition of NFPA 72 for installations in the U.S.

The detectors can be tested individually using the DPU (refer to
the DPU manual, P/N 315-033260) or with the Model 8720
Programming Unit (refer to the 8720 Manual, P/N 315-033260FA).

MAINTENANCE

No special maintenance procedures are required for the HI921.
The control unit automatically indicates the trouble message for
any detector. This detector may need replacement.

CAUTION:

  UNDER NO CIRCUMSTANCES IS THE

DETECTOR HEAD TO BE DISASSEMBLED. NO REPAIRS
SHOULD BE ATTEMPTED.

DO NOT PAINT

The detector/base plastic is marked 

DO NOT PAINT

. This is

intended to prohibit painting during routine maintenance of the
occupancy which can affect proper operation of the detector.

Figure 2

Installation and Wiring Diagram

A6V10323932_a_en_--

Siemens Industry, Inc.
Building Technologies  Division
Florham Park, NJ

WIRING

Detector bases for Model HI921 should be connected as shown
in Figure 2.

DETECTOR MOUNTING

To ensure proper installation of the detector head into the base,
be sure the wires are properly dressed at installation:

• Position all wires flat against the base.

• Take up all slack in the outlet box

• Route wires away from connector terminals.

TO INSTALL DETECTOR HEAD:

• Rotate detector counterclockwise while gently pressing on

it until the detector seats fully into base.

• Then rotate the detector clockwise until it stops and locks in

place. Insert optional locking screw (Order Model LK-11).

TO REMOVE DETECTOR HEAD:

• Loosen locking screw, if installed. Then rotate the detector

counterclockwise until stop is reached.

• Pull detector out of base.

OPTIONAL
REMOTE
ALARM
INDICATOR
MODELS
RL-HW / RL-HC

TO NEXT BASE

TO NEXT BASE

DO NOT
USE AN
END OF
LINE
DEVICE

DETECTOR BASE
MODEL DB-11/DB-11E

LINE 1**

LINE 2**

5

6

1a

TB1

TB3

TB2

1b

5

6

1a

1b

RELAY*
CONTACTS
3A, 120 VAC
3A, 30 VDC

REMOTE RELAY
BASE MODEL DB2-HR

*The relay contacts are shown after System reset, which represents the non-alarm condition.

**HI921 is a polarity insensitive detector. Line 1 and Line 2 can be either line of the loop.

5+

NO

C

NC

6–

5+

NO

C

NC

6–

DO NOT
USE AN
END OF
LINE
DEVICE

FROM ADDRESSABLE
DEVICE CIRCUIT OF A
COMPATIBLE CONTROL
UNIT OR PREVIOUS
ADDRESSABLE DEVICE

Siemens Canada Limited
Building Technologies  Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada