Intelligent Control Point

Installation Instructions
Model HCP

INTRODUCTION

The Model HCP Intelligent Control Point from Siemens
Industry, Inc. provides remote, independent control of
any of the following:

1. A notification appliance circuit (NAC)
2. A telephone zone (XLS only)
3. A speaker zone (25V or 70.7V RMS)  (XLS only,

FV2025/2050, FV922/924)

The HCP communicates through the DLC device loop
card of the FireFinder-XLS System, the FS-DLC device
loop card of the FS-250 System, the FC922/FV922,
FC2025/FV2025 periphery FCI2016 Board (250p)
detector circuits, and the FC2050/FV2050, FC924/FV924
FCI2017 periphery board (500p) detector circuits. Each HCP
uses one device address on the device loop.

PROGRAMMING

Use the DPU Programmer/Tester to program and test the module.

The HCP may only be assigned addresses 1 to 60. It is recommended to program
the HCP devices first to ensure that enough addresses have been reserved for them.
Other devices may then be assigned to addresses in this range that were not
assigned to an HCP.

Disconnect wire at terminal 1 and 2 on  TB1 before programming.

To set the HCP device address:

 •

Plug the programming cable of the DPU Programmer/Tester into the two-
pin programming points on the HCP. (See Figure 1 for location.)

Set the device address for the HCP by following the instructions in the 

DPU

Programmer/Tester Manual, 

P/N 315-033260.

Each HCP can be assigned a custom message using either the Zeus Programming Tool
(XLS System), the FS-CT2 (FS-250 System), the FC2025/2050, FV2025/2050 FSX2002
Engineering Tool, or the FC922/924, FV922/924 FSX7212 Engineering Tool. Refer to
the Zeus Quick Start Manual, P/N 315-033875, or the FS-250 Programming Manual, P/
N 315-049403, as applicable.

PROGRAMMING
POINTS

DEVICE

ADDRESS:

DISCO

NNECT

WIRE

AT TE

RMINAL

"1" & "2"

SIEMENS

INDUSTR

Y, INC.

CAUT

ION

ON TB

1 BEF

ORE P

ROGR

AMMIN

G

FLORHAM

PARK,

NJ, 07932

INSTALLA

TION

INSTRUCTIONS

TB2 O

N BAC

K SID

E

P/N 315-034860

SIEMENS

MODEL:

HCP

TB1 O

N BAC

K SID

E

6

5

4

3

2

1

1

2

3

4

5

6

Figure 1

HCP Intelligent Control Point

Summary of Contents for HCP

Page 1: ... module The HCP may only be assigned addresses 1 to 60 It is recommended to program the HCP devices first to ensure that enough addresses have been reserved for them Other devices may then be assigned to addresses in this range that were not assigned to an HCP Disconnect wire at terminal 1 and 2 on TB1 before programming To set the HCP device address Plug the programming cable of the DPU Programme...

Page 2: ...er XLS FS 250 Desigo FC2025 2050 FV2025 2050 Cerberus PRO FC922 924 FV922 924 Systems through its addressable device loops These loops are connected to the DLC via terminal blocks on the CC 5 or CC 2 cardcage XLS or to the FS DLC viaTB3 on the FS MB FS MB2 main board FS 250 They may be wired Class A Style 6 or Class B Style 4 Figure 2 shows both wiring types and the connections to the DLC See the ...

Page 3: ... HCP TB1 1 2 HCP TB1 1 2 ZONE 1 ZONE 2 DLC LOCATED IN ONE SLOT OF CC 5 CC 2 HCP TB1 1 2 HCP TB1 1 2 4 3 2 1 CLASS A WIRING CLASS B WIRING HCP TB1 1 2 HCP TB1 1 2 HCP TB1 1 2 HCP TB1 1 2 1 1 2 2 X1401 X1402 X1801 X1802 4 3 2 1 1 1 2 2 Detector circuits on periphery board for FC922 FV922 FC2025 FV2025 X1401 X1402 X1801 X1802 Figure 2 FireFinder XLS Device Loop Connections NOTES 1 Loop resistance 50 ...

Page 4: ... FireFinder XLS FS 250 System control panel the Desigo FC2025 2050 FV2025 2050 Operating Unit and the Cerberus PRO FC922 924 FV922 924 Operating Unit For FS 250 Systems the NAC circuit must be set to always on in the panel or FS CT2 configuration tool See the Line Resistance table below for the allowable line resistance for each HCP output circuit E C N A T S I S E R E N I L T I U C R I C T U P T ...

Page 5: ...XLS System only as shown in Figure 5 the 24 VDC provides power to the supervision and call in detection circuitry If the 24 VDC is lost a trouble condition displays on the PMI PMI 2 of the FireFinder XLS The HCP provides a dial tone when a Fireman s Master telephone FMT is taken off hook or when a Portable FireFighter s telephone PFT is jacked in Each HCP can support a maximum of 5 phones off hook...

Page 6: ...RAMMING POINTS PROGRAMMING POINTS REFER TO PAD 4 INSTALLATION INSTRUCTIONS P N 315 050217 FOR PROPER SETTING OF SWITCH 4 THE AUXILIARY POWER OUTPUT MUST BE CONFIGURED TO ALWAYS ON Figure 6 HCP Used As A Telephone Zone HCP As 70 7V 25V Speaker Zone in an XLSV System When the HCP is used as a speaker zone FireFinder XLS System only the 24 VDC provides power to the supervision circuitry If the 24 vol...

Page 7: ...ker zone wire length for various wire gauge sizes is shown in Figure 7 for the 70 7V option and in Figure 8 for the 25V option Connect the speaker output as Style Z Class A or StyleY Class B as shown in Figures 10 and 11 100 0 0 05 0 10 0 15 0 20 0 25 200 300 400 500 600 TOTAL SPEAKER ZONE WIRE LENGTH FEET dB LOSS 700 800 900 1000 SPEAKER LOAD 25 WATTS AT 70 7V RMS LOCATED AT END OF RUN DOES NOT I...

Page 8: ...IO OUTPUT 70 7 25 VRMS 40 WATTS MAX POWER LIMITED STYLE Z SUPERVISED SPEAKER ZONE CONNECTIONS SUPV 14 VDC 1mA ACTIVATED 70 7 V 25V RMS 25 WATTS MAX 24K W 5 EOL RESISTOR P N 140 034677 EARTH SHIELD HCP STYLE Y SUPERVISED SPEAKER ZONE CONNECTIONS SUPV 14 VDC 1mA ACTIVATED 70 7 V 25V RMS 25 WATTS MAX CAPACITOR COUPLED 70 7V 25V RMS SPEAKERS 24K W 5 EOL RESISTOR P N 140 034677 EARTH SHIELD HCP 24K W 5...

Page 9: ...TS MAX POWER LIMITED STYLE Z SUPERVISED SPEAKER ZONE CONNECTIONS SUPV 14 VDC 1mA ACTIVATED 70 7 V 25V RMS 25 WATTS MAX 24K W 5 EOL RESISTOR P N 140 034677 EARTH SHIELD HCP STYLE Y SUPERVISED SPEAKER ZONE CONNECTIONS SUPV 14 VDC 1mA ACTIVATED 70 7 V 25V RMS 25 WATTS MAX CAPACITOR COUPLED 70 7V 25V RMS SPEAKERS 24K W 5 EOL RESISTOR P N 140 034677 EARTH SHIELD HCP 24K W 5 EOL RESISTOR P N 140 034677 ...

Page 10: ...ISED SPEAKER ZONE CONNECTIONS SUPV 14 VDC 1mA ACTIVATED 70 7 V 25V RMS 25 WATTS MAX 24K W 5 EOL RESISTOR P N 140 034677 EARTH SHIELD HCP STYLE Y SUPERVISED SPEAKER ZONE CONNECTIONS SUPV 14 VDC 1mA ACTIVATED 70 7 V 25V RMS 25 WATTS MAX CAPACITOR COUPLED 70 7V 25V RMS SPEAKERS 24K W 5 EOL RESISTOR P N 140 034677 EARTH SHIELD HCP 24K W 5 EOL RESISTOR P N 140 034677 68K 1 4W 5 EOL RESISTOR ON LAST HCP...

Page 11: ...h deep plaster ring extension 2 Connect the field wiring 3 Insert the HCP into the box and fasten the device plate to the box 4 Cover the device front plate with the 5 inch switchplate supplied and fasten with two plate screws 4 INCH SQUARE BOX 2 1 8 INCHES DEEP DOUBLE GANG BOX 3 1 2 INCHES DEEP HCP HCP SWITCHPLATE 5 INCHES SQUARE SUPPLIED SWITCHPLATE 5 INCHES SQUARE SUPPLIED 1 1 2 INCH DEEP EXTEN...

Page 12: ...security concept that is customized to individual security needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components us...

Reviews: