Siemens GER Instructions, Installation, Operation, Maintenance Download Page 6

Vehicle Description

Vehicle Function and Operational Interlocks
Type GER vacuum circuit breakers are comprised of the
interrupter/operator module fitted to a vehicle.  This inter-
rupter/operator module is an integral arrangement of op-
erating mechanism, dielectric system, vacuum interrupt-
ers, and means of connecting the primary circuit.  The ve-
hicle supports the interrupter/operator module, providing
mobility and fully coordinated application in GE Metal-Clad
type M26 and M36 switchgear.

This manual should be used jointly with the Circuit Breaker
Operator manual, SGIM-9918 (3AH) or SG-3398 (3AF).

Alignment
All aspects of the circuit breaker structure which impact
alignment and interchangeability are checked at the fac-
tory.  Field adjustment will not normally be required, but
variations in existing switchgear may require field adjust-
ment.

Recommended Tools

• Racking Crank: Original circuit breaker racking crank

may be used.

Installing Circuit Breaker Module Into Compartment

Interlock

Trip-Free/Spring Dump Interlock
The Trip-Free/Spring Dump interlock is of primary
importance in the safe and effective operation of the type
GER Vertical Lift Replacement circuit breaker.  This interlock
provides safety to both personnel and equipment during
the racking procedure, as it prevents the electrical or
manual closing and/or electrical spring charging of the
circuit breaker until the circuit breaker is in either the
Disconnect/Test position or the Connect position.

It is important to note the Trip-Free/Spring Dump interlock
on the type GER circuit breaker is functionally similar to
the original manufacturer’s interlock, however, there are
differences among the two interlocking systems which
must be discussed.

Hazardous voltages and high-speed
moving parts. Will cause death, serious
injury, and property damage.

De-energize before working on this equip-
ment.

Do not by-pass interlocks or otherwise make
interlocks inoperative.

4

Inoperative or by-passed interlocks will cause
death, serious personal injury and property
damage.

Mechanical and electrical interlocks are pro-
vided as integral components of this equip-
ment to ensure safe use.  Interlocks must be
in operation at all times.  Read this instruc-
tion manual.  Know and understand correct
interlock function.  Check interlock function
prior to inserting circuit breaker into
switchgear cubicle.

Differences
The original manufacturer’s trip-free and spring dump
interlocking is a two stage system.  In this system, the
spring dump is accomplished in one stage, and occurs via
a ramp located on the left side of the cubicle working in
concert with a linkage system.  The springs are dumped as
the circuit breaker is rolled in or out from the Disconnect
position as the circuit breaker linkage is actuated by the
cubicle mounted ramp.

The second stage of the original manufacturer’s system
addresses the trip-free condition of the circuit breaker.  In
this system the circuit breaker is held trip-free during
racking via the trip roller located on the right side of the
circuit breaker, working in concert with the moveable cam
plate associated with the elevating mechanism.  The circuit
breaker is held trip-free during racking as the trip roller is
displaced by the moveable cam.

Another distinct difference among the two systems is that
the original manufacturer’s circuit breaker must be
manually “tripped” (opened) prior to attempting to rack
the circuit breaker.

The trip-free/spring dump arrangement on the Siemens
type GER replacement circuit breaker is integrated into a
single stage interlocking system.  Trip-free operation, spring
dump and circuit breaker “tripping” (opening) all result
from the single linkage arrangement operated by the trip-
free roller located on the right side of the circuit breaker,
which works in concert with the moveable car mounted in
the original switchgear cubicle.  There is no spring dump
linkage located on the left side of the type GER circuit
breaker and manual tripping of the circuit breaker prior to
racking is not required as both of these functions occur
instantaneously with the initiator displaced by the
moveable cam in much the same manner as the original
manufacturer’s circuit breaker.

The function of the type GER circuit breaker trip-free/spring
dump interlocking will be discussed in greater detail.

Summary of Contents for GER

Page 1: ...Instructions Installation Operation Maintenance SGIM 9978B Vacuum Circuit Breakers Vehicle Type GER 5kV to 15kV ...

Page 2: ...rts should not be used in the repair of the equipment Follow all safety instructions contained herein IMPORTANT The information contained herein is general in nature and not intended for specific application purposes It does not relieve the user of responsibility to use sound practices in application installation operation and mainte nance of the equipment purchased Siemens reserves the right to m...

Page 3: ...Interlock 4 Differences 4 Circuit Breaker in Disconnect Test Position Refer to Figure 4 5 Trip Free In Racking Procedure Refer to Figure 2 6 Circuit Breaker in Connect Position Refer to Figure 3 7 Adjustment Procedure Trip Free Spring Dump 8 MOC Actuator Refer to Figure 4 9 Continuous Current Interlock 9 Maintenance 10 Introduction and Maintenance Intervals 10 Recommended Maintenance and Lubricati...

Page 4: ...ountered by the user These words are defined as Danger Indicates an imminently hazardous situation which if not avoided will result in death or serious in jury Warning Indicates a potentially hazardous situation which if not avoided could result in death or serious injury Caution indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury Dangerous Proce...

Page 5: ...ng pallet for later use if the breaker is to be stored prior to its installation 2 Inspect for concealed damage Notification to carrier must take place within 15 days to assure prompt reso lution of claims 3 Each circuit breaker should be appropriately lifted us ing lifting sling rated for at least 3 000 lbs The circuit breaker shall be lifted by Upper B phase post insula tor 4 The palleted circui...

Page 6: ...ctrical interlocks are pro vided as integral components of this equip ment to ensure safe use Interlocks must be in operation at all times Read this instruc tion manual Know and understand correct interlock function Check interlock function prior to inserting circuit breaker into switchgear cubicle Differences The original manufacturer s trip free and spring dump interlocking is a two stage system...

Page 7: ...cates that the circuit breaker is open with closing springs discharged In this condition parts relating to the closing and spring charging are not engaged as is indicated by the location of pawl roller latching pawl pawl and pawl roller Note also that the trip pushed cam trip free pushrod interlock levers motor cutoff switch are in their lowest position It is recommended that the trip free spring ...

Page 8: ...ing Dump Interlock Circuit Breaker in Mid Cycle Racking Position As shown in the enlarged view of the circuit breaker operator the displacement of the trip free roller results in the downward displacement of the trip actuator which in turn lifts the lever linkage which results in the elevation of the interlock levers The upward displacement of the interlock levers result in the opening on the norm...

Page 9: ...e Preparation page 3 for cubicle adjustment In the Connect position with the trip free roller residing as required in the upper cavity of the moveable cam the circuit breaker is now free to perform all required functions The enlarged view of the operating mechanism shows the circuit breaker operator closed with springs charged Note that all items displaced during the racking procedure have returne...

Page 10: ...ller counter clockwise resulting in the immediate discharge of the closing spring and the opening of the circuit breaker 2 Rack the circuit breaker to a position between Connect and Disconnect Test Repeat steps 1 2 and 3 listed in the procedure detailed in section entitled Trip Free Racking Should any problems arise with the trip free spring dump interlock follow the adjustment procedure listed be...

Page 11: ...lacement of the original GE 52STA with a Siemens 52STA 5kV 250MVA P N 18 669 255 502 and for all other ratings P N 18 669 255 501 If requested the Siemens type GER circuit breakers can come equipped with a MOC actuator This is provided to actuate the original manufacturer s designated 52STA auxiliary switch mounted in the existing cubicle The Siemens MOC actuator has a total travel from circuit br...

Page 12: ...problems arise which are not covered sufficiently for the Purchaser s purposes the mat ter should be referred to the local Siemens sales office Removal from Switchgear Prior to performing any inspection or maintenance checks or tests the circuit breaker must be removed from the switchgear The Installation and Initial Functional Tests section describes the removal procedure in detail Princi pal ste...

Page 13: ...tion of this manual for special instructions and precautions regarding removal of a circuit breaker which is not at floor level Maintenance Checks of the Primary Power Path The primary power path consists of the three vacuum interrupters and the six primary studs These components are checked for cleanliness and condition Figure 6 The vacuum interrupters are discussed in the Circuit breaker Operato...

Page 14: ...liding rotating and articulating surfaces MOC Actuator System MOC Actuator System should be inspected refer to Table 2 Periodical Maintenance and Lubrication Tasks Maintenance of the circuit breaker MOC actuator system DOES NOT mitigate the requirement to maintain cubicle mounted MOC system components These shall be main tained in accordance with the OEM s recommendations Electrical Control Checks...

Page 15: ...second withstand refer to Circuit Breaker Operator Manual SGIM 9918 for ratings Insulation Barriers and all Insulating Components 1 Cleanliness 2 Cracking crazing tracking or other sign of deterioration Interrupter Operator Mechanism 1 Cleanliness 2 Lubrication of sliding rotating and articulating surfaces Apply Anderol 732 aerosol synthetic fluid grease part number 15 172 816 058 or Beacon 325 pa...

Page 16: ...9978B 12 2003 Printed in U S A 2001 Siemens Power Transmission Distribution Inc SIEMENS is a registered trademark of Siemens AG Siemens Power Transmission Distribution Inc P O Box 29503 Raleigh NC 27626 0503 ...

Reviews: