Instructions for use the GENESIS II Control Panel 

 

Overview 

The GENESIS II, makes it possible to install single-

zone fire detection based on a conventional intrusion 

detection control panel, controlling and supervising a 

2-wire line, equipped with up to 32 conventional de-

tectors at 24Vdc. 
The GENESIS II is supplied with 13.8Vdc from the 

intrusion control panel and, by means of an internal 

converter, is able to provide the 24Vdc supply re-

quired by the detectors and/or call points. This elimi-

nates the need for an external 24Vdc power supply 

and battery backup, as in the case of mains failure /-

disconnection, the intrusion control panel backup 

powers the system. 

Jumper settings 

Description ON 

OFF 

Non current limited detectors 

 

PU1 

PU2 

Current limited detectors 

PU1

PU2 

 

Fault Output C-NC 

PU3 

(2,3) 

 

Fault Output C-NO 

PU3 

(1,2) 

 

Local Control  

(Push button GENESIS II) 

PU4  

Remote control  

(from Intrusion control panel) 

 PU4 

LED displays 

LED Colour Description 

DL1 Green Enable 

LED 

DL2 Red  Fire 

LED 

DL3 

Amber 

Short Circuit fault LED 

DL4 

Amber 

Open Circuit fault LED 

Wiring 

Power supply and control. 

GENESIS II has two control possibilities, depending 

on the fact that the Intrusion Control Panel has an 

output for sensors rearming or not. 
Follow the steps detailed here below: 

–  Carry the supply (11 to 14Vdc) from the Intrusion 

Control Panel to the terminals designated (-12V+) 

of GENESIS II. 

–  If the Intrusion Control Panel does not include the 

aforementioned output for detectors rearming, the 

control on GENESIS II will be carried out from the 

reset push-button itself (make sure that the PU4 

jumper has been inserted). 

–  In case the Intrusion Control Panel has the output 

available, wire it at the input of the terminals input 

labelled (CONT) of GENESIS II. It will be reset 

when it detects a level of 0V in that control input; 

this implies a rearming in the detectors line if that 

level is present during the period required by the 

detectors (3 to 4 seconds is usually enough for 

most of them). To have this feature available, you 

must remove the PU4. 

Detectors and/or call points line. 

Connect the detectors (ionizing, optical, etc) and/or 

call points line to (+LINE-) as shown in fig.1.  
 

 

 

The GENESIS  II

 

allows both current-limited 

and non-current-limited detectors and/or call 

points provided that the two types are 

not 

mixed on the same line. 

 

Setup 

Set up the GENESIS II according to the type used as 

follows: 

Non-current-limited detectors and/or call points: 

Remove GENESIS II jumpers PU1 and PU2.  

See Fig.1 
Compatibility with the non-current detectors below: 

– DL0  

 

beam detector 

–  DF1191/92  

infrared flame detector 

Current-limited detectors and/or call points 

Insert GENESIS II jumpers PU1 and PU2.  

See Fig.1 
Compatibility with the current detectors below: 

– OP320C  

optical detector 

– OH320C  

multi detector 

– HI320C   

heat detector 

– HI322C   

heat detector 

–  MT320C  

manual call point 

Alarm and fault output 

It incorporates alarm and fault outputs by means of 

voltage-free relay contacts, what facilitates its adap-

tation to the different Intrusion Control Panels, re-

gards to connection. 
Figures 2 and 3 show, as an example, 2 types of 

connection, among the most common ones, used for 

this kind of installations: 

–  Figure 2 presents a typical connection for the iden-

tification of alarm and fault on the detectors line of 

GENESIS II, in two independent zones associated 

to the Intrusion Control Panel. 

–  In those Intrusion Panels with EOL resistor in each 

zone, being possible to program some of them as 

“fire zone” so that a short-circuit or open-circuit in 

that zone will be identified as fire alarm or fault, re-

spectively, the wiring can be done as shown in 

fig.3, which includes an electrical diagram for a 

better comprehension. 

–  In addition to the connection shown in figure 2, 

fig.3 presents the possibility of tamper detection on 

the part of the GENESIS II box. 

Functional test 

Before testing the installation ensure that the power 

supply polarity is correct. Also, check that jumpers 

PU1 and PU2 are in the correct positions according 

to the type of detectors used in the installation.  
Next, connect the GENESIS II to power and check 

that the green “ENABLED” led is lit and that the In-

trusion Control Panel is in standby mode. 
 

Open-circuit fault. 

–  Disconnect the 2K7 end of line resistor. The amber 

“OC FAULT” led on the GENESIS II will be lit and 

the Intrusion Control Panel indicate fault on the 

corresponding zone. 

–  Reconnect the resistor. The indicator will go out.  

–  Remove each of the detectors from their sockets 

one at a time (the line will open as each is re-

moved provided the standard mounting instruc-

tions for the detectors have been followed). Check 

that unit in exactly the same was as described in 

the previous paragraph. 

 

Short-circuit fault 

–  Short-circuit the 2K7 end of line resistor. The am-

ber “SC FAULT” led on the GENESIS II will be lit 

and the Intrusion Control Panel will indicate fault 

on de corresponding zone. Remove the short-

circuit. The indicator will go out. 

 

Alarm

 

–  Now activate each detector by means of the effect 

it is designed to detect (smoke, rapid temperature 

rise, manual call point activation etc). The indicator 

on the detector will be lit, as will the “ALARM” led 

on the GENESIS II. The Intrusion Control Panel 

will indicate alarm on the corresponding zone. 

 

Resetting the detector lines 

–  From the reset push-button of GENESIS II, or from 

a sensors rearming output, in case the Intrusion 

Control Panel allows it, cause a 3 seconds rearm-

ing approximately in the detectors line, checking 

that during this period of time, the “ENABLED” 

LED of GENESIS II will go out, so that if the cause 

that originated the activation of the detectors has 

disappeared, the detectors will go back to standby 

condition. 

Technical data 

 

 

General features 

 

Dimensions in mm  

(wide x height x depth) 

 
134 x 85 x 27cm 

Aprox. Weight (gr.) 

125gr 

Temperature and relative humidity  

without condensation. 

0

0

 - 50

0

C  

10% - 90% 

 

 

Standards 

CE 

EN50130-4 

9

 

EN61000-6-3 

9

 

89/336/EEC 

9

 

93/68/EWG 

9

 

 

 

Electrical features 

 

Supply voltage 

11 - 14V. 

Stand-by consumption  

(with no detectors) 

35 - 45mA 
 

Max. consumption 

<200mA 

Establishment timing since rearming 

<500ms. 

Delay timing of alarm signal 

<300ms 

 

 

Output features 

 

Alarm output by voltage-free contacts 

C NO NC 

30Vd.c. 1A 
 

Fault output by voltage-free contacts  

C-NO or C-NC 

30Vd.c. 1A 
 

 
Line characteristics for PU1 and PU2  

for non-current-limited detectors OFF 

Power supply voltage 

11 - 14V 

Line voltage with detectors in stand-by,  

17.5 - 22.5V 

Line voltage in alarm condition 

6 - 10V. 

Line consumption to indicate alarm 

18 - 56mA. 

Line consumption to indicate short-

circuit. 

59 - 65mA 

Line consumption to indicate open-

circuit 

<4mA 

Maximum consumption of stand-by  

detectors 

<4mA 
 

End-of-line resistor 

2K7 Ohm 1/2W 

+/-10% 

 
Line characteristics for PU1 and PU2  

for current-limited detectors ON 

Line voltage with detectors in stand-by 

11 -14V

 

Line voltage in alarm condition 

18.5 - 24V 

Line consumption to indicate alarm 

17 - 22.5V 

Line consumption to indicate short-

circuit. 

25 - 58mA 

Line consumption to indicate open-

circuit 

60 - 75mA 
 

Maximum consumption of stand-by  

detectors 

<4mA 

End-of-line resistor 

2K7 Ohm 1/2W 

+/-10% 

Details for ordering 

 

Type Part 

no Designation 

MGEN2 9300170001 

Fire 

detection 

panel 

PCB 

GEN2-DE 9300150001 Fire 

detection 

panel 

German 

GEN2-EN 

9300110001 

Fire detection panel  

English 

GEN2-ES 

9300100001 

Fire detection panel  

Spanish 

GEN2-PL 9300090001 Fire 

detection 

panel 

Polish 

GEN2-IT 930012.0-001 

Fire 

detection 

panel 

Italian 

GEN2-

SV(SE) 

9300130001 

Fire detection panel  

Swedish 

GEN2-FR) 9300180001  Fire 

detection 

panel 

French 

GEN2-NL 

9300190001 

Fire detection panel  

Netherlands 

GEN2-NO 

9300140001 

Fire detection panel  

Norwegian 

 

 

 

Reviews: