10.1.2.4 Out of Service
The GCP5000 (GCE) supports Out of Service Operation using the D OOS IPs option.
Figure 10-8 shows the options available for the
D OOS IPs
option mode. The designer
selects which OOS inputs are associated with each PSO. The Out of Service1.. 5 selections will
be available in the
System Inputs
so that they can be assigned to vital inputs.
To take a PSO out of service the maintainer will need to energize the Out of Service input and
then using the display select which component to take out of service. When any component is
OOS or an OOS input is energized the maintenance call light will be turned off. Thus, if the
maintainer forgets to de-energize the OOS Inputs the maintenance call will remain off.
The maintainer can select a new OOS timeout at the time when they set the unit out of service.
Figure 10-8 Out of Service, D OOS IPs