background image

 

GAMMA wave 

Technical Product Information 

February 2007 

Switch actuator wave GE 561/01 

5WG3 561-4AB01 

 

 

Siemens AG 

wave GE 561/01, 6 pages 

Technical Manual 

Automation and Drives Group 

 

 

Electrical Installation Technology 

©

 Siemens AG 2007 

Update: http://www.siemens.de/gamma 

P.O. Box 10 09 53, D-93009 Regensburg  

Subject to change without prior notice 

 

 

2.20.8.1/5 

 

Programming the radio sensor to the corresponding 
channel of the switch actuator is complete. 
 

Note:

 There is only a limited time available for connec-

tion, since the switch actuator wave exits the special 
function after approx. 2 minutes. 
 
If connection fails (e.g., if the distance between the 
switch actuator and the radio sensor is too great), the 
switch actuator wave exits the special function after 
approx. 2 minutes without confirming success by rapid 
flashing. The LED clears. 
If further radio sensors are to be connected to the two 
channels of the switch actuator wave, this operation 
should be repeated. 
 

Deleting a connection: 

Deleting a connection is carried out by reassignment 
(Diagram F). 
To delete a connection between a radio sensor and a 
channel of the switch actuator wave carry out the follow-
ing steps 1 and 2 one after the other: 
 

1.

  Activate the “special function channel A“ in the switch 

actuator wave (brief actuation of the pushbutton for 
(F2) no more than 3 seconds) or “special function 
channel B” (long actuation of the pushbutton (F2) for 
the duration of 3 to 6 seconds). 

 

2

.  Trigger the sending of the program telegrams at the 

radio sensor to be programmed (see operating in-
structions for the corresponding device). 

 
The connection of the radio sensor wave to the corre-
sponding channel of the switch actuator wave is thus de-
leted. 
 

Deleting all the connections and resetting the switch 
actuator wave to the supplied state: 

 
Action:   Very long actuation of the pushbutton (F2) for 

at least 10 seconds. 

Display:   After 3 seconds the LED (F3) will flash once 

briefly (approx. 0.1 sec.). After 10 seconds the 
LED flashes rapidly for the duration of approx. 
3 seconds with approx. 2.5 Hz (3 times per 
sec.). 

 
All connections to channels A and B of the switch actua-
tor are deleted. The device is in the supplied state. 
If the pushbutton remains pushed for a maximum of 3 
seconds or for 3 to 6 seconds after resetting to the sup-
plied state, it will be directly switched to the “special 
function channel A” or “special function channel B“. 

Time-switch operation (on-period 1 to 60 minutes): 

 
The two channels of the switch actuator wave can be 
operated respectively as a time switch. The connected 
loads are thereby switched off automatically after a time 
that can be set in steps of one minute. The on period 
can be retriggered and is reset and restarted with each 
receipt of an “ON” command via radio. With the receipt 
of an “OFF” command it is switched off immediately. 
 
The time-switch operation is activated or deactivated via 
the “special function channel A” or the “special function 
channel B”. 
 
 

Activating the time-switch operation. 

To activate the time-switch operation with an on-period 
that can be set in steps of one minute in the range of 1 
to 60 minutes, carry out the following steps 1A or 1B, 2, 
3, and 4 one after the other: 
 

1A. Switch on special function channel A. 

Action:   Brief actuation of pushbutton (F2) for the du-

ration of no more than 3 seconds. 

Display:   The LED (F3) begins to flash slowly within 3 

seconds of the release of the pushbutton with 
approx. 0.5 Hz (once in 2 seconds). 

 

or 

1B. Switch on special function channel B. 

Action:   Long actuation of the pushbutton (F2) for the 

duration of 3 to 6 seconds. 

Display:   After 3 seconds the LED (F3) flashes briefly 

once (approx. 0.5 sec.). Within 3 to 6 seconds 
after the release of the pushbutton the LED 
shows a steady light. 

 

2. Select time-switch operating mode. 

Action:   Actuate the pushbutton (F2) again for the du-

ration of no more than 9 seconds. 

Display:   The LED (F3) clears after the actuation of the 

pushbutton, and after the release of the 
pushbutton within no more than 9 seconds 
flashes quickly for the duration of approx. 3 
seconds with approx. 2.5 Hz (3 times per 
sec.). 

 

3. Set on period in steps of 1 minute. 

To set the on period in steps of one minute, actuate the 
pushbutton (F2) again according to the desired on pe-
riod. Each actuation of the pushbutton extends the on 
period by 1 minute (e.g., 1 pushbutton actuation = 1 
minute on period, 5 actuations of the pushbutton = 5 
minute on period, etc.). 

Summary of Contents for GAMMA wave GE 561/01

Page 1: ...led on the top of the device and an LED to display the operation condi tions in the special function operating mode The Special Function operating mode includes the fol lowing functions Connecting radio sensors with the function switching ON OFF or scene Activating deactivating the time switch function Clearing connections to radio sensors Resetting the device to the supplied state Technical Speci...

Page 2: ...ctural factors e g reinforced concrete or electric electronic sources of interference A distance of at least 1 m must be maintained be tween the transmitter and the relevant receivers Although the radio transmission occurs in the safe 868 MHz frequency band interference in the radio transmission cannot be ruled out The radio transmission used is not suitable for secu rity applications V DANGER The...

Page 3: ...iver will be reduced and telegram losses may thereby occur 1 2 3 4 5 Kanal 1 L 1 N L 2 Kanal 2 C1 C2 C3 C4 Diagram C C1 Screw terminals C2 Wire fixing C3 Pushbutton C4 LED 1 2 L1 3 N 4 L2 5 Diagram D Terminal assignment Diagram D 1 Load output channel A 2 L1 Power supply L for actuator electronics and channel A 3 N Power supply N for actuator electronics 4 L2 Power supply L for channel B 5 Load ou...

Page 4: ...utton F2 for the duration of up to 3 seconds switches the actuator to the special function channel A operating mode This is displayed by a slow flashing with approx 0 5 Hz once in 2 seconds of the LED F3 Special function for channel B A long actuation of the pushbutton F2 for the duration of 3 to 6 seconds switches the actuator to the special function channel B operating mode This is displayed by ...

Page 5: ... B of the switch actua tor are deleted The device is in the supplied state If the pushbutton remains pushed for a maximum of 3 seconds or for 3 to 6 seconds after resetting to the sup plied state it will be directly switched to the special function channel A or special function channel B Time switch operation on period 1 to 60 minutes The two channels of the switch actuator wave can be operated re...

Page 6: ...F3 begins to flash slowly once in 2 seconds with approx 0 5 Hz upon release of the pushbutton within 3 seconds or 1B Switch on special function channel B Action Long actuation of the pushbutton F2 for the duration of 3 to 6 seconds Display After 3 seconds the LED F3 flashes briefly approx 0 1 sec once After the release of the pushbutton within 3 to 6 seconds the LED shows a steady light 2 Select t...

Reviews: