Document No. 563-002
Installation Instructions
October 1, 2005
VAV BOX
VAV BOX
VAV BOX
WL
AN0017R1
Figure 2.
FLNX Mounting Options, no enclosure.
Remote Mount Antenna
The FLNX is mounted inside the TEC (or any metal)
enclosure and the antenna is brought through a 1/2”
knockout (Figure 3).
The antenna extension cable 12” long.
WLAN0016R1
Figure 3.
Mounting Inside Enclosure.
Installation
1. Determine the optimal location of the FLNX and
antenna for RF communications.
2. Mount the FLNX using screws, double-sided tape
or velcro (included).
3. Connect the communication port of the FLN
device to the FLNX.
4. Connect 24 Vac power (Figure 4).
Page 2 of 4