3
Building Technologies
A6V10361100_b_en_--
Fire safety and security products
07.2012
Connection diagram
5
1a
6
1b
Connect to
collective input
module
FDB181C
5
1a
6
1b
FDB181C
5
1a
6
1b
FDB181C
EOL
1.
5KE
20
CA
Maintenance
Performance test
Recommendation:
– Submit all detectors to an annual visual check. Detectors that are strongly soiled or
mechanically damaged must be replaced.
– Long term backup detectors should be stored with plastic bag.
– Carry out heat test each year.
Technical data
Operating voltage
10 … 28 VDC
Operating current (quiescent)
≤
0.1 mA
Activation current
≤
60.0 mA
Alarm temperature
61 °C
±
3
℃
Operating temperature
–10 ... +50 °C
Storage temperature
–20 ... +70 °C
Humidity
≤
96% (40
Color
White, RAL 9010
Protection category GB4208-93
IP40
Details for ordering
Type
Material No.
Part No.
Designation
Weight
FDT181C
S54320-F12-A2
101190983
Collective heat detector
0.065Kg
FDB181C
S54320-F9-A2
101190980
Collective detector base
0.038Kg