Siemens FDT181C Product Manual Download Page 3

3

 

Building Technologies

 

 

A6V10361100_b_en_-- 

Fire safety and security products 

 

07.2012 

 

Connection diagram 

 

5

1a

6

1b

Connect to 

collective input 

module

FDB181C

5

1a

6

1b

FDB181C

5

1a

6

1b

FDB181C

EOL

1.

5KE

20

CA

 

Maintenance  

 

 

Performance test 

Recommendation:  
–  Submit all detectors to an annual visual check. Detectors that are strongly soiled or 

mechanically damaged must be replaced. 

–  Long term backup detectors should be stored with plastic bag.  
–  Carry out heat test each year. 

Technical data 

 

 

Operating voltage 

10 … 28 VDC 

Operating current (quiescent) 

0.1 mA 

Activation current 

60.0 mA 

Alarm temperature 

61 °C

±

 

Operating temperature 

–10 ... +50 °C 

Storage temperature 

–20 ... +70 °C 

Humidity 

96% (40 

Color  

White, RAL 9010 

Protection category GB4208-93 

IP40 

 

Details for ordering  

Type  

Material No. 

Part No. 

Designation  

Weight  

FDT181C 

S54320-F12-A2

 

101190983 

Collective heat detector  

0.065Kg 

FDB181C 

S54320-F9-A2

 

101190980 

Collective detector base 

0.038Kg 

Summary of Contents for FDT181C

Page 1: ...erature Collective detector no address setting polarity free connection 360 visible alarm indicator Resistant to environment and interference factors such as humidity corrosive and vibration with immunity against electro magnetic interference Application Communication with FC18 controller via FDCI183 transponder each FDCI183 can connect max 32 collective detectors Communication with BC80 controlle...

Page 2: ... mounting Install the base and finish the wiring during the construction phase 1 Insert detector into base and turn it clockwisely until positioning pointer on base align with positioning pointer on detector see below Uninstallation 1 Turn it counterclockwisely and pull the detector out of base After all the construction is finished the dust cap must be taken away No painting Dimensions In mm with...

Page 3: ...st be replaced Long term backup detectors should be stored with plastic bag Carry out heat test each year Technical data Operating voltage 10 28 VDC Operating current quiescent 0 1 mA Activation current 60 0 mA Alarm temperature 61 C 3 Operating temperature 10 50 C Storage temperature 20 70 C Humidity 96 40 Color White RAL 9010 Protection category GB4208 93 IP40 Details for ordering Type Material ...

Page 4: ...ctronics Limited No 1 Fengzhidonglu Xibeiwang HaiDian District Beijing 100094 China Tel 10 6476 8806 Fax 10 6476 8899 Data and design subject to change without notice Doc No A6V10361100_b_en_ Manual FD18 Edition 07 2012 101190971 ...