Siemens FDT181 Product Manual Download Page 3

3

 

Building Technologies

 

 

A6V10214490_a_en_-- 

Fire safety and security products 

 

03.2010 

 

Connection diagram 

 

Maintenance  

 

l

 

Performance test 

Recommendation:  

  Submit all detectors to an annual visual check. Detectors that are strongly soiled or 

mechanically damaged must be replaced. 

  Any detectors should be replaced after 7 to 10 years of service, independent from 

the environmental conditions. 

  Long term auxiliary detectors should be stored with plastic bag.  

  Carry out heat test each year. 

Teconical data 

 

 

Operating voltage 

12 

 32 VDC 

Operating current (quiescent) 

0.26 mA 

Activation current 

1.2 mA 

Operating temperature 

10 ... +50 

°

Storage temperature 

20 ... +75 

°

Humidity 

96% (40

±

Communication protocol 

FD18-BUS 

Color  

White, RAL 9010 

Protection category GB4208-93 

IP44 

 

Details for ordering  

Type  

Material No. 

Part No. 

Designation  

Weight  

FDT181 

S54320-F3-A1 

100856212 

Heat detector  

0.064Kg 

FDB181 

S54320-F1-A1 

100856213 

Detector base 

0.027Kg 

 

A5Q00022001 

100566011 

FDT181 dust cap 

 

Summary of Contents for FDT181

Page 1: ...o operation modes A2S A2R Automatically address setting without encoder setting or DIP switch All around visible alarm indicator Resistant to environment and interference factors such as humidity electro magnetic interference corrosive and vibration Communication via FD18 BUS polarity free connection Sticker Method easy for commissioning Functions The detection behavior of the detectors is influen...

Page 2: ...its operating status See table Detector Indicator Normal Off Locate Test Flashing Alarm Steady on Installation l Easy and time saving mounting Install the base and finish the wiring during the construction phase 1 Point the retaining nest to the positioning pointer and insert it into the base 2 Turn it clock wisely until it stops Uninstallation 1 Turn it counterclockwisely until it stops 2 Pull th...

Page 3: ...ditions Long term auxiliary detectors should be stored with plastic bag Carry out heat test each year Teconical data Operating voltage 12 32 VDC Operating current quiescent 0 26 mA Activation current 1 2 mA Operating temperature 10 50 C Storage temperature 20 75 C Humidity 96 40 2 Communication protocol FD18 BUS Color White RAL 9010 Protection category GB4208 93 IP44 Details for ordering Type Mate...

Page 4: ...Xinxi Road Shangdi Information Industry Base Haidian District Beijing 100085 China Tel 10 6296 2255 Fax 10 6298 7387 www sbt siemens com Data and design subject to change without notice Doc No A6V10214490_a_en_ Version a Manual FD18 Edition 03 2010 ...

Page 5: ...izSoft PDF Password Remover With the trial version only the first 5 pages of each file can be exported To get all the pages exported you need to purchase the software from http www anypdftools com buy buy pdf password remover html ...