![Siemens FDT181 Product Manual Download Page 3](http://html.mh-extra.com/html/siemens/fdt181/fdt181_product-manual_383371003.webp)
3
Building Technologies
A6V10214490_a_en_--
Fire safety and security products
03.2010
Connection diagram
Maintenance
l
Performance test
Recommendation:
–
Submit all detectors to an annual visual check. Detectors that are strongly soiled or
mechanically damaged must be replaced.
–
Any detectors should be replaced after 7 to 10 years of service, independent from
the environmental conditions.
–
Long term auxiliary detectors should be stored with plastic bag.
–
Carry out heat test each year.
Teconical data
Operating voltage
12
…
32 VDC
Operating current (quiescent)
0.26 mA
Activation current
1.2 mA
Operating temperature
–
10 ... +50
°
C
Storage temperature
–
20 ... +75
°
C
Humidity
≤
96% (40
±
2
℃
)
Communication protocol
FD18-BUS
Color
White, RAL 9010
Protection category GB4208-93
IP44
Details for ordering
Type
Material No.
Part No.
Designation
Weight
FDT181
S54320-F3-A1
100856212
Heat detector
0.064Kg
FDB181
S54320-F1-A1
100856213
Detector base
0.027Kg
A5Q00022001
100566011
FDT181 dust cap