Undertaking modernization
4
Step 1: Detector modernization
17
Building Technologies
A6V10323158_d_en_--
Fire Safety
2015-04-09
4 Undertaking modernization
4.1 Step 1: Detector modernization
The following steps must be taken during each modernization:
1. Check whether the base needs replacing [
2. Configuration of detector type [
3. Parameterization of detection characteristics [
4. Test the detectors [
The 'Configuration of detector type' step is only needed for the following detector
families:
l
AnalogPLUS
l
Interactive
l
SIGMALOOP
l
In the case of the detector family 'MS8/PMT' and all other collective systems,
the detector type is defined by selecting detection characteristics during
parameterization.
4.1.1 Base replacement
On MS8, AnalogPLUS, SIGMALOOP, and collective detector lines, when replacing
the point detector with a multiple protocol detector, the switch can be made to a
Sinteso detector base.
To modernize MS8, AnalogPLUS, and SIGMALOOP detector lines, use the
following detector bases:
l
FDB221
l
FDB222
To modernize collective detector lines, use the following detector bases:
l
FDB201
l
FDB202
When modernizing interactive detector lines, it is not possible to switch to Sinteso
detector bases.