Undertaking modernization
Step 1: Detector modernization
24
Building Technologies
A6V10323158_d_en_--
Fire Safety
2015-04-09
Operation as
detector of type:
Selected parameter set in the
control panel configuration
Active parameter set and emulation
mode on the detector
DO1151A
DO1152A
APS005S
'OO' Universal mode (1)
APS006S
'OO' Sensitive mode (3)
APS007S, APS009S
'OO' Super Sensitive mode (5)
DO1153A
APS073SH
'OO' Super Sensitive mode (5)
APS070SH, APS071SH,
APS072SH
'OO' Ultra Sensitive mode (6)¹
DOT1151A
DOT1152A
APS083S²
Manned:
'OOT' High Suppression mode (8)¹
Unmanned:
'OOT' Balanced mode (4)
APS084S
'OOT' Suppression mode (5)
APS005S, APS06S, APS015S,
APS019S, APS009S,
APS082S ³
'OOT' Balanced mode (4)
APS007S, APS085S
'OOT' Fast Response mode (6)
APS081S
High Sensitive Fast 'OOT' mode (9)
APS080S
'OOT' Super Sensitive mode (11)
DT1152A
APS100T
'T' A1R mode (1)
APS105T
'T' BR mode (2)
APS103T
'T' A1S mode (3)
APS107T
'T' BS mode (4)
¹ Does not meet the criteria of EN 54-7
² This parameter set is applied differently in the modes 'Manned' and 'Unmanned'
³ The static activation temperature is 80 °C in emulation mode instead of 70 °C for
the parameter set APS082S
You will find more information in documents 007227 and 009718.
See the chapter 'Applicable documents [
7]'.