7BSpecifications
54BTechnical data FDOOT221, FDOOT241-x / -Ax
8
119 | 138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
Ambient conditions
Permissible operating temperature:
●
FDOOT221
-10…+60 °C
●
FDOOT241-8/-9/-A3/-A4
-25…+70 °C
●
FDOOT241-A
-35…+70 °C
●
FDOOT241-A5
-25…+70 °C
●
FDOOT241-A9
-35…+70 °C
Storage temperature:
●
FDOOT221 / FDOOT241-x/-Ax
-30…+75 °C
●
FDOOT241-A
-35…+75 °C
●
FDOOT241-A9
-35…+75 °C
Air humidity
≤95
% rel.
Protection categories (IEC 60529):
●
Base FDB2x1/FDB2x1-AA/FDB2x2,
IP43
●
with base attachment FDB291
IP43
●
Base FDB2x1 and sealing element
FDBZ295
IP44
●
Base adapter FDB241, FDB299, FDB251,
FDB281
IP44
●
Sounder base FDSB29x
IP43
●
Base attachment wet FDB295
IP44
Electromagnetic compatibility:
●
1 MHz…2 GHz
50 V/m
Permissible wind speed:
●
FDOOT221
Max. 5 m/s
●
FDOOT241-x/-Ax
Max. 20 m/s
Mechanical data
Color
∼RAL
9010 pure white
Standards
European standards
●
EN 54-7
●
EN 54-17
●
EN 54-5 for FDOOT241-x/-Ax
●
CEA 4021