Building Technologies 

 

A6V10201150_a_en_--

Fire Safety & Security Products 

 

05.06.2008

2

 

Safety 

2.1

 

Safety notices 

The safety notices must be observed in order to protect people and property. 
The safety notices in this document contain the following elements: 

z

 

Symbol for danger 

z

 

Signal word 

z

 

Nature and origin of the danger 

z

 

Consequences if the danger occurs 

z

 

Measures or prohibitions for danger avoidance 

Symbol for danger 

 

 

This is the symbol for danger. It warns of risks of injury. 
Follow all measures identified by this symbol to avoid injury or death. 

Additional danger symbols 
These symbols indicate general dangers, the type of danger or possible 

consequences, measures and prohibitions, examples of which are shown in the 

following table. 
 

 

General danger 

Explosive atmosphere 

 

Voltage/electric shock 

Laser light 

 

Battery 

Heat 

Summary of Contents for FDM1101-Rx

Page 1: ...Building Technologies Fire Safety Security Products FDM1101 Rx Manual call point collective Technical manual ...

Page 2: ...t and in the subject thereof By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part nor to make them available to any third party without our prior express written authorization nor to use it for any purpose other than for which it was delivered to him ...

Page 3: ...el 16 3 4 1 3 Plastic insert 16 3 4 1 4 Glass insert 16 3 4 2 Optional accessories 17 3 4 2 1 Key FDMK295 17 3 4 2 2 Protective cover FDMC295 17 3 4 2 3 Plastic inserts FDMP295 x 17 3 4 2 4 Glass inserts FDMG295 x 18 3 4 2 5 Back box FDMH295 R 18 3 4 2 6 Back box FDMH295 S 18 3 4 2 7 Metal cable gland M20 x 1 5 18 3 4 2 8 Back nut M20 x 1 5 19 3 4 2 9 Connection terminal DBZ1190 AB 19 4 Project en...

Page 4: ...4 Building Technologies A6V10201150_a_en_ Fire Safety Security Products 05 06 2008 8 Specifications 26 8 1 Technical data 26 8 2 Dimensions 27 8 3 Environmental compatibility 27 9 Index 28 ...

Page 5: ...tion z Has suitable specialist training for the function project scale and product range z Has attended the Project Manager training courses Installer z Assembles and installs the components at the place of installation z Performs a subsequent check of the installation z The personnel have received specialist training in the area of building installation technology or electrical installations Comm...

Page 6: ...element End Of Line collective Unaddressed detector line Document identification Location Meaning Title page z Short name z Name in full z Document purpose Last page bottom left hand side z Document no number modification index language COUNTRY z Date of issue Last page bottom right hand side z Manual z Register Revision history Document no Edition date Brief description A6V10201150_a_en_ 06 2008 ...

Page 7: ... of the danger z Consequences if the danger occurs z Measures or prohibitions for danger avoidance Symbol for danger This is the symbol for danger It warns of risks of injury Follow all measures identified by this symbol to avoid injury or death Additional danger symbols These symbols indicate general dangers the type of danger or possible consequences measures and prohibitions examples of which a...

Page 8: ...oided CAUTION CAUTION identifies a dangerous situation which could result in slight to moderately serious injury if this situation is not avoided NOTE Note identifies possible damage to property that may result from non observance Symbol for risk of injury Information about the risk of injury is shown as follows WARNING Nature and origin of the danger Consequences if the danger occurs z Measures p...

Page 9: ...e with the electrotechnical regulations z If possible de energize products on which commissioning maintenance or repair work is being undertaken z Lock areas that have been de energized so that they cannot be switched back on by mistake z Label connection terminals with an external source of voltage using a DANGER external source of voltage board z Separately route feeders to products and fuse the...

Page 10: ...r any potential panic responses z Inform people of any noise or mist that may be produced z Inform the relevant points that will receive alarms and faults before testing remote transmission Changes to the system layout and products Modifications to the system and to individual products may lead to faults malfunctioning and safety risks The written consent of Siemens and the relevant safety bodies ...

Page 11: ...ies or damage to property caused by disregarding safety instructions in the documentation or on the product z Personal injuries or damage to property caused by poor maintenance or lack of maintenance Exclusion of liability We have checked the content of this document for compliance with the described hardware and software Nevertheless deviations cannot be excluded therefore we do not offer any gua...

Page 12: ... and a switching unit Two back boxes are available as options for surface mounted feed lines Back box FDMH295 R does not have pre drilled holes for surface mounted feed lines Back box FDMH295 S has two holes and grommets on its top and can be used for surface mounted feed lines with a cable diameter of 5 mm The activation button can either be actuated using a resettable plastic insert or a breakab...

Page 13: ...ert FDM1101 RP F S54371 F6 A6 Collective manual call point with plastic insert for France FDM1101 RG F S54371 F6 A5 Collective manual call point with glass insert for France 3 2 Setup 3 2 1 Connections Manual call points FDM1101 Rx have 4 connection terminals on their rear for the detector line At the end of the collective detector line a control panel specific line termination element EOL must be...

Page 14: ...3 2 2 Indication elements Manual call points FDM1101 Rx have a red LED Only the optical fiber can be seen from the outside 1 LED in manual call point FDM1101 Rx 1 Red LED for Alarm LED red Meaning off Normal operation flashes light in intervals of 1 s or is permanently on depending on the control panel Alarm ...

Page 15: ...nger Normal condition 3 Alarm Fire Comment The evaluation of the danger level and the decisions to be taken e g activation of remote transmission are configured in the control panel 3 3 2 Test mode A test mode can be set on the control panel to test the manual call point When in test mode alarms from the manual call points are not forwarded by the control panel The manual call points can be tested...

Page 16: ...for manual call points that are not in use z in different languages z compatible with manual call points FDM1101 Rx FDM1101A Rx FDM225 FDM226 3 4 1 3 Plastic insert A plastic insert UK FDMP295 is enclosed in the delivery of each manual call point FDM1101 RP A plastic insert France FDMP295 F is enclosed in the delivery of each manual call point FDM1101 RP F See also Plastic inserts FDMP295 x J 17 3...

Page 17: ...open the unit z compatible with manual call points FDM1101 Rx FDM1101A Rx FDM225 xx FDM226 xx z order no 10 pcs per pack A5Q00013448 3 4 2 2 Protective cover FDMC295 z protective cover against unwanted activation z compatible with manual call points FDM1101 Rx FDM1101A Rx FDM225 xx FDM226 xx z order no 10 pcs per pack A5Q00013440 3 4 2 3 Plastic inserts FDMP295 x z The following plastic inserts ca...

Page 18: ...226 xx 3 4 2 5 Back box FDMH295 R z red back box for installation of the manual call point with surface mounted feed lines z compatible with manual call points FDM1101 Rx FDM1101A Rx FDM225 xx z order no 10 pcs per pack A5Q00013437 3 4 2 6 Back box FDMH295 S z red back box for installation of the manual call point with surface mounted feed lines z has 2 holes on its top with grommets for cables of...

Page 19: ...y Products 05 06 2008 3 4 2 8 Back nut M20 x 1 5 z compatible with metal cable gland M20 x 1 5 z order no 100 pcs per pack A5Q00004479 3 4 2 9 Connection terminal DBZ1190 AB z 3 poles z for wire diameters 1 2 5 mm2 z to connect the cable shieldings z order no 50 pcs per pack 4942340001 ...

Page 20: ... systems with collective SynoLINE600 signal processing Refer to List of compatibility doc no 008331 for details 4 2 Ranges of application The manual call points are intended for use in places where a fire can be detected by people who can manually trigger an alarm 4 3 Installation site The manual call points must be installed in easily accessible places at a height of 1 3 1 6 m ...

Page 21: ... the shieldings to a connection terminal to be ordered separately The shieldings must not touch any other potentials or metal parts in the device 3 Connect the detector line Connect only one wire to each terminal 4 Insert a line termination element EOL at the end of each collective detector line into the connection terminal The line termination element depends on the type of control panel 5 Remove...

Page 22: ... 05 06 2008 WARNING Deactivating the manual call points prevents alarms from being forwarded The alarm does not take place z Deactivated manual call points must be labeled with the NOT IN USE label LINE LINE EOL FDM1101 Rx Detector line connection diagram EOL Line termination element End Of Line ...

Page 23: ...ng Technologies A6V10201150_a_en_ Fire Safety Security Products 05 06 2008 6 Commissioning The collective detector line is commissioned on the control panel The exact procedure is described in the control panel documentation ...

Page 24: ...er special maintenance work is necessary 7 2 Testing detector with the key NOTICE False alarm Switch the manual call point to Test on the control panel Procedure 1 2 Testing 1 Insert the key into the manual call point until the switching unit moves Ö The manual call point has been triggered 2 To arm the manual call point pull out the key again Ö The switching unit is in a straight position and the...

Page 25: ...s pane is pushed in enabling trouble free removal of the glass Procedure A B Removing cover 1 Remove the cover of the manual call point using the key movements A and B 2 Remove the broken glass insert from the switching unit 3 Insert a new glass insert Be sure to tension the spring with the glass insert 4 Refit the cover 7 4 Spare parts You will find spare parts in the Optional accessories chapter...

Page 26: ...t of compatibility doc no 008331 Detector line z Design Screw terminals Connections z Wire cross section 0 28 1 5 mm2 Environmental conditions Operating temperature 25 70 C Storage temperature 30 75 C Air humidity 95 rel Protective category IP44 Electromagnetic compatibility at z 10 MHz 1 GHz 50 V m z 1 GHz 2 GHz 10 V m Mechanical data Dimensions L x W x H z FDM1101 Rx 87 x 87 x 20 mm z FDM1101 Rx...

Page 27: ...registered z FDM1101 RG registered z FDM1101 RP F registered z FDM1101 RG F registered Protection categories IEC 60529 QA standards z Siemens Standard SN 36350 z ISO9001 z ISO9004 CE conformity mark yes 8 2 Dimensions 87 87 53 35 5 20 36 5 1 36 5 4 4 2 Dimensional drawings for FDM1101 Rx and back box FDMH295 R FDMH295 S 8 3 Environmental compatibility Electronic components and synthetic materials ...

Page 28: ...ing glass insert 26 C Collective Communication 12 Communication Collective 12 Cover Remove 22 E EOL Line termination element 13 K Key Testing detector 25 L Line termination element EOL 13 M Manual call point Test mode 15 R Red LED Alarm indicator 14 Remove Cover 22 Replacing Broken glass insert 26 S Surface mounted feed lines Back box 12 T Test mode Manual call point 15 Testing detector Key 25 ...

Page 29: ...Index 29 Building Technologies A6V10201150_a_en_ Fire Safety Security Products 05 06 2008 ...

Page 30: ...Gubelstrasse 22 CH 6301 Zug Tel 41 41 724 24 24 Fax 41 41 723 35 22 www siemens com buildingtechnologies 2008 Copyright Siemens Switzerland Ltd Technical specifications and availability subject to change without notice Document no A6V10201150_a_en_ Manual DS11 1 Edition 05 06 2008 Register 4 ...