background image

FDM1101-Rx
Manual call point collective

Technical Manual

A6V10201150_d_en_--

Building Technologies

2018-12-19

Control Products and Systems

Summary of Contents for FDM1101-R Series

Page 1: ...FDM1101 Rx Manual call point collective Technical Manual A6V10201150_d_en_ Building Technologies 2018 12 19 Control Products and Systems ...

Page 2: ...nication thereof to others without express authorization are prohibited Offenders will be held liable for payment of damages All rights created by patent grant or registration of a utility model or design patent are reserved Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Theilerstrasse 1a CH 6300 Zug Tel 41 58 724 2424 www siemens com buildingtechnologi...

Page 3: ...tup 16 3 2 1 Connections 16 3 2 2 Indication elements 16 3 3 Function 17 3 3 1 Danger levels 17 3 3 2 Test mode 17 3 4 Accessories 18 3 4 1 Key 18 3 4 2 NOT IN USE label 18 3 4 3 Plastic insert 18 3 4 4 Glass insert 18 3 4 5 Optional accessories 19 3 4 5 1 Key FDMK295 19 3 4 5 2 Protective cover FDMC295 19 3 4 5 3 Plastic inserts FDMP295 x 19 3 4 5 4 Glass inserts FDMG295 x 20 3 4 5 5 Back box FDM...

Page 4: ... 5 1 Installation 25 6 Commissioning 26 7 Maintenance Repair 27 7 1 Performance check 27 7 2 Testing detector with the key 27 7 3 Replacing the glass insert 28 7 4 Spare parts 28 8 Specifications 29 8 1 Technical data 29 8 2 Dimensions 30 8 3 Environmental compatibility and disposal 30 Index 31 ...

Page 5: ...e project according to schedule Provides the information required to run the project Has obtained suitable specialist training for the function and for the products Has attended the training courses for Project Managers Installation personnel Assembles and installs the product components at the place of installation Carries out a performance check following installation Has received specialist tra...

Page 6: ... of international standard ISO 8601 format YYYY MM DD Conventions for text marking Markups Special markups are shown in this document as follows Requirement for a behavior instruction 1 2 Behavior instruction with at least two operation sequences Version option or detailed information for a behavior instruction Intermediate result of a behavior instruction End result of a behavior instruction Numb...

Page 7: ...ty for Sinteso product line 1 2 Download center You can download various types of documents such as data sheets installation instructions and license texts via the following Internet address http siemens com bt download l Enter the document ID in the Find by keyword input box You will also find information about search variants and links to mobile applications apps for various systems on the home ...

Page 8: ...ws this document s revision history Version Edition date Brief description d 2018 12 19 Editorial adjustments c 2017 10 31 DBZ1190 AB Conductor cross section adapted 0 5 2 5 mm2 b 2017 02 06 Source language and reference document Applicable documents Download center Conventions for text marking Technical terms and Revision history sections added in About this document chapter Product version ES an...

Page 9: ...l dangers the type of danger or possible consequences measures and prohibitions examples of which are shown in the following table General danger Explosive atmosphere Voltage electric shock Laser light Battery Heat Signal word The signal word classifies the danger as defined in the following table Signal word Danger level DANGER DANGER identifies a dangerous situation which will result directly in...

Page 10: ...ry is shown as follows WARNING Nature and origin of the danger Consequences if the danger occurs Measures prohibitions for danger avoidance How possible damage to property is presented Information about possible damage to property is shown as follows NOTICE Nature and origin of the danger Consequences if the danger occurs Measures prohibitions for danger avoidance ...

Page 11: ...idance and supervision of a qualified electrician in accordance with the electrotechnical regulations Wherever possible disconnect products from the power supply when carrying out commissioning maintenance or repair work on them Lock volt free areas to prevent them being switched back on again by mistake Label the connection terminals with external voltage using a DANGER External voltage sign Rout...

Page 12: ... may be produced Before testing the remote transmission inform the corresponding alarm and fault signal receiving stations Modifications to the system design and the products Modifications to the system and to individual products may lead to faults malfunctioning and safety risks Written confirmation must be obtained from Siemens and the corresponding safety bodies for modifications or additions M...

Page 13: ... injury and damage to property in the event of a fire Read the Release Notes before you plan and or configure a fire detection installation Read the Release Notes before you carry out a firmware update to a fire detection installation NOTICE Incorrect planning and or configuration Important standards and specifications are not satisfied Fire detection installation is not accepted for commissioning...

Page 14: ...and a switching unit Two back boxes are available as options for surface mounted feed lines Back box FDMH295 R does not have pre drilled holes for surface mounted feed lines Back box FDMH295 S has two holes and grommets on its top and can be used for surface mounted feed lines with a cable diameter of 5 mm The activation button can either be actuated using a resettable plastic insert or a breakabl...

Page 15: ... and the type plate Details of the product version can be found after the device order number Figure 3 Example of a product label with details of the product version Depending on the product and various approvals the product labels may differ in terms of the information type and layout Look for your device s order number on the product label You will find the product version after the order number...

Page 16: ... end of line element EOL must be connected to the terminals Figure 4 Connection diagram for FDM1101 Rx EOL Line termination element End Of Line 3 2 2 Indication elements The manual call points FDM1101 Rx have a red LED Only the optical fiber can be seen from the outside Figure 5 LED in manual call point FDM1101 Rx 1 Red LED for Alarm LED red Meaning Off Normal operation Flashes light in intervals ...

Page 17: ...rmal state no danger 3 Alarm The evaluation of the danger level and the resulting measures e g activation of remote transmission are configured on the control panel 3 3 2 Test mode The manual call points can also be tested with the key A test mode must be set on the control panel to test the manual call points When in test mode alarms from the manual call points are not forwarded by the control pa...

Page 18: ...1101 Rx FDM1101A Rx FDM225 FDM226 3 4 3 Plastic insert A plastic insert UK FDMP295 is enclosed in the delivery of each manual call point FDM1101 RP A plastic insert France FDMP295 F is enclosed in the delivery of each manual call point FDM1101 RP F See also 2 Plastic inserts FDMP295 x 19 3 4 4 Glass insert A glass insert UK FDMG295 is enclosed in the delivery of each manual call point FDM1101 RG A...

Page 19: ...ll point FDM226 Rx Radio manual call point FDM275 Order number A5Q00013448 3 4 5 2 Protective cover FDMC295 For protection against unintended alarm activation Compatible with Manual call point FDM1101 Rx Manual call point FDM1101A Rx Manual call point FDM225 Rx Manual call point FDM226 Rx Radio manual call point FDM275 Order number A5Q00013440 3 4 5 3 Plastic inserts FDMP295 x For alarm activation...

Page 20: ...442 Order number for glass insert FDMG295 F France A5Q00013443 3 4 5 5 Back box FDMH295 R For using manual call points with surface mounted cable entry No pre drilled holes for the feed lines Color Red Compatible with Manual call point FDM1101 Rx Manual call point FDM1101A Rx Manual call point FDM225 Rx Order number A5Q00013437 3 4 5 6 Back box FDMH295 S For using manual call points with surface m...

Page 21: ...x 1 5 Compatible with back boxes Order number 10 pcs per pack A5Q00004478 3 4 5 8 M20 x 1 5 metal counter nut For use with metal cable gland M20 x 1 5 Order number A5Q00004479 3 4 5 9 Connection terminal DBZ1190 AB 3 poles For conductor cross sections of 0 5 2 5 mm2 To connect the cable shieldings Order number 50 pcs per pack 4942340001 ...

Page 22: ...or use in places where a fire can be detected by people who can manually trigger an alarm 4 3 Installation site The manual call points must be mounted in easily accessible places at a height of 1 3 1 6 m Observe the country specific regulations for the exact mounting height 4 4 Environmental influences If the devices are used in industrial applications consultation with the project manager is requ...

Page 23: ...ielded connect the shieldings to a connection terminal to be ordered separately The shielding must not touch any other potentials or metal parts in the device 3 Connect the detector line Only connect one wire per terminal 4 Insert an end of line element EOL at the end of each collective detector line into the terminals The end of line element is specific to the control panel 5 Remove the cover cap...

Page 24: ...ety 2018 12 19 WARNING Deactivating the manual call points prevents alarms from being forwarded The alarm is not triggered Deactivated manual call points must be labeled with the NOT IN USE notice Figure 7 Detector line connection diagram EOL Line termination element End Of Line LINE LINE EOL FDM1101 Rx ...

Page 25: ...tted to carry out installation work Incorrect installation can take safety devices out of operation unbeknown to a layperson CAUTION Electrical voltage on lines Risk of injury due to electric shock During mounting and installation work electrical voltage must not be applied to the lines Note the positive and negative poles Only connect one wire per terminal This is the only way to ensure the conne...

Page 26: ...26 32 Building Technologies A6V10201150_d_en_ Fire Safety 2018 12 19 6 Commissioning The collective detector line is commissioned on the control panel The exact procedure is described in the control panel documentation ...

Page 27: ...necessary You will find more detailed information in the fire detection system documentation 7 2 Testing detector with the key NOTICE False alarm Switch the manual call point to Test on the control panel Procedure Figure 8 Testing 1 Insert the key into the manual call point until the switching unit moves a The detector is triggered 2 To arm the manual call point pull out the key again a The insert...

Page 28: ...ushed in making it possible to remove the glass insert easily Procedure Figure 9 Removing the cover cap 1 Remove the cover cap of the manual call point using the key movements A and B 2 Remove the broken glass insert from the switching unit 3 Insert a new glass insert Be sure to tension the spring with the glass insert 4 Refit the cover cap 7 4 Spare parts You will find spare parts in the Optional...

Page 29: ...ty doc no 008331 Connections Detector line Design Screw terminals Cable cross section 0 28 1 5 mm2 Ambient conditions Operating temperature 25 70 C Storage temperature 30 75 C Air humidity 95 rel Protection category IEC60529 IP44 Electromagnetic compatibility at 10 MHz 1 GHz 50 V m 1 GHz 2 GHz 10 V m Mechanical data Dimensions L x W x H FDM1101 Rx 87 x 87 x 20 mm FDM1101 Rx with back box FDMH295 R...

Page 30: ...following measures have been undertaken Use of reusable materials Use of halogen free plastics Electronic parts and synthetic materials can be separated Larger plastic parts are labeled according to ISO 11469 and ISO 1043 The plastics can be separated and recycled on this basis The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disp...

Page 31: ...nvironmental influences 22 EOL End of line 16 ES Product version 15 G Glass insert Replace 28 I Impact Chemicals 22 Moisture 22 Temperature 22 K Key Testing detectors 27 27 M Maintenance intervals 27 Manual call point Test mode 17 O Original language 6 P Packaging label Product version 15 Product label Product version 15 R Recycling 30 Red LED Alarm indicator 16 Remove Cover cap 23 Replace Glass i...

Page 32: ...nternational Headquarters Theilerstrasse 1a CH 6300 Zug 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2008 Technical specifications and availability subject to change without notice Document ID A6V10201150_d_en_ DS11 1 Edition 2018 12 19 ...