Commissioning
6
This chapter gives instructions to commissioning your device, see Local commissioning
(Page 93).
Furthermore, the device can be commissioned using SIMATIC PDM, see Commissioning with
6.1
Basic safety notes
WARNING
Improper commissioning in hazardous areas
Device failure or risk of explosion in hazardous areas.
● Do not commission the device until it has been mounted completely and connected in
accordance with the information in Installing/mounting (Page 37).
● Before commissioning take the effect on other devices in the system into account.
WARNING
Commissioning and operation with pending error
If an error message appears, correct operation in the process is no longer guaranteed.
● Check the gravity of the error.
● Correct the error.
● If the error still exists:
– Take the device out of operation.
– Prevent renewed commissioning.
CAUTION
Loss of type of protection
Damage to device if the enclosure is open or not properly closed. The type of protection
specified on the nameplate or in Technical data (Page 215) is no longer guaranteed.
● Make sure that the device is securely closed.
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA
91