Maintenance
29
Siemens Building Technologies
007995_a_en_--.doc
Fire & Security Products
04.2004
6.5 Simulate
fault
Overview
By simulating a fault it is possible to check the remote transmission equipment for
faults (e.g. transmission to the fire brigade).
WARNING!
Before simulating a fault, inform accordingly to avoid an unnecessary turning
out.
Procedure
Simulate a fault as follows:
1.
Inform accordingly on the pending simulation.
2.
Press the numerical key '2' and keep it pressed.
3.
Press the zone key '1'.
A fault is simulated.
The yellow zone LED is flashing rapidly.
The fault sequence has been activated.
4.
Check whether the fault sequence is correct.
5.
To finish the simulation, press the key 'Reset'.