Installation

Purpose

The DOW1171 wireless radio smoke detector (Fig. 1, [2])
is used in conjunction with the FDCW221 radio gateway in
FDnet-compatible fire detection systems or in conjunction
with the DCW1151 radio gateway in the AlgoRex fire
detection system.
Up to 30 radio smoke detectors can be connected to a
radio gateway over a maximum distance of 40 m.
The radio smoke detector is screwed into the DBW1171
base (Fig. 1, [1]).

Preparation

Ensure that there is a radio connection between the radio
smoke detector, in its intended installation site, and the
radio gateway.
When determining where to site the base (Fig. 3), ensure
that the alarm indicator [3] can be clearly seen from the
investigation route [4].

Installation

1.

Use 2 screws to fit the base on a plane surface (Fig. 4
and Fig. 5). Note the minimum spacing specified (Fig. 2)
and the position of the alarm indicator [5] marked on the
base [1].

2.

If necessary, plug a labeled DBZ1193A detector
designation plate (Fig. 4, [6]) into the base [1].

3.

If necessary, insert a detector locking device (Fig. 6, [7])
in the base [1].

è

A radio smoke detector screwed in the base can only
be unlocked using a screwdriver.

4.

Only place the batteries in the radio smoke detector
when commissioning.

Commissioning

When commissioning the radio smoke detector,
note the documents 009865 and 001787.

Register the radio smoke detector on the radio gateway as
described in doc. no. 009865 and/or 001787.

de

Montage

Verwendungszweck

Der drahtlose Funk-Rauchmelder DOW1171 (Fig. 1, [2])
wird zusammen mit dem Funk-Gateway FDCW221 in
FDnet-fähigen Brandmeldesystemen oder mit dem Funk-
Gateway DCW1151 im AlgoRex-Brandmeldesystem
eingesetzt.
Bis zu 30 Funk-Rauchmelder können über eine maximale
Distanz von 40 m an einen Funk-Gateway aufgeschaltet
werden.
Der Funk-Rauchmelder wird in den Sockel DBW1171
(Fig. 1, [1]) eingeschraubt.

Vorbereitung

Stellen Sie sicher, dass der Funk-Rauchmelder vom
vorgesehenen Montageort aus eine Funkverbindung zum
Funk-Gateway hat.
Legen Sie die Montagelage (Fig. 3) des Sockels fest,
damit der Alarmindikator [3] vom Erkundungsweg [4] aus
gut sichtbar ist.

Montage

1.

Montieren Sie den Sockel mit 2 Schrauben auf einer
planen Oberfläche (Fig. 4 und Fig. 5). Beachten Sie die
einzuhaltenden Minimalabstände (Fig. 2) und die
markierte Position des Alarmindikators [5] auf dem
Sockel [1].

2.

Stecken Sie bei Bedarf ein beschriftetes Melder-
Kennzeichnungsschild DBZ1193A (Fig. 4, [6]) in den
Sockel [1].

3.

Setzen Sie bei Bedarf eine Melderarretierung (Fig. 6,
[7]) in den Sockel [1] ein.

è

Ein im Sockel eingeschraubter Funk-Rauchmelder
kann nur mit einem Schraubenzieher entriegelt
werden.

4.

Setzen Sie die Batterien erst bei der Inbetriebnahme in
den Funk-Rauchmelder ein.

Inbetriebnahme

Beachten Sie zur Inbetriebnahme des Funk-
Rauchmelders die Dokumente 009865 und
001787.

Melden Sie den Funk-Rauchmelder gemäss der
Beschreibung in den Dokumenten 009865 bzw. 001787
am Funk-Gateway an.

Summary of Contents for DOW1171

Page 1: ... detector Base de Funk Rauchmelder Sockel fr Détecteur de fumée hertzien Embase es Detector de humos inalámbrico Zócalo it Rivelatore di fumo wireless Base 1 2 en Installation de Montage fr Montage es Montaje it Montaggio Fig 1 500 mm 20 mm 2 3 4 Fig 2 Fig 3 6 5 1 Ø 4 mm 47 70 4 1 41 5 ø 118 5 5 1 Fig 4 Fig 5 ...

Page 2: ...se DBW1171 2 Détecteur de fumée hertzien DOW1171 3 Indicateur d alarme 4 Trajectoire de balayage 5 Marquage d indicateur d alarme 6 Porte étiquette DBZ1193A 7 Verrou de détecteur DBZ1190 es Leyenda 1 Zócalo DBW1171 2 Detector de humos inalámbrico DOW1171 3 Indicador de alarma 4 Recorrido de exploración 5 Marca del indicador de alarma 6 Placa de designación del detector DBZ1193A 7 Dispositivo de bl...

Page 3: ...1787 Register the radio smoke detector on the radio gateway as described in doc no 009865 and or 001787 de Montage Verwendungszweck Der drahtlose Funk Rauchmelder DOW1171 Fig 1 2 wird zusammen mit dem Funk Gateway FDCW221 in FDnet fähigen Brandmeldesystemen oder mit dem Funk Gateway DCW1151 im AlgoRex Brandmeldesystem eingesetzt Bis zu 30 Funk Rauchmelder können über eine maximale Distanz von 40 m...

Page 4: ...ateway conformément à la description dans le doc n 009865 ou 001787 es Montaje Uso previsto El detector de humos inalámbrico DOW1171 Fig 1 2 se utiliza junto con el gateway inalámbrico FDCW221 en los sistemas de detección de incendios que soportan FDnet o junto con el gateway inalámbrico DCW1151 en el sistema de detección de incendios AlgoRex A un gateway inalámbrico pueden conectarse hasta 30 det...

Page 5: ... della base in modo che l indicatore di allarme 3 sia ben visibile dal percorso d ispezione 4 Montaggio 1 Montare la base con 2 viti su una superficie piana Fig 4 e Fig 5 Osservare le distanze minime da rispettare Fig 2 e la posizione dell indicatore di allarme 5 evidenziata sulla base 1 2 All occorrenza inserire nella base 1 una piastra di identificazione rilevatore DBZ1193A Fig 4 6 con dicitura ...

Page 6: ... de 9 V 2 bloques it Rivelatore di fumo wireless completo incl base DBW1171 batteria al litio 9 V 2 blocchi DBW1171 S24218 F316 A1 en Base de Sockel fr Embase es Zócalo it Base FDBH291 A5Q00004439 en Detector heating unit de Melderheizung fr Élément chauffant es Calefactor del detector it Riscaldatore rivelatore DBZ1190 BPZ 4585260001 en Detector locking device de Melderarretierung fr Verrou de dé...

Page 7: ...soussigné Siemens déclare que l équipement radioélectrique du type DOW1171 est conforme à la directive 2014 53 UE Le texte complet de la déclaration UE de conformité est disponible à l adresse internet suivante http siemens com bt download fichier CED DOW1171 DECLARACIÓN UE DE CONFORMIDAD SIMPLIFCADA Por la presente Siemens declara que el tipo de equipo radioeléctrico DOW1171 es conforme con la Di...

Page 8: ... Gubelstrasse 22 CH 6301 Zug Tel 41 41 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2008 Technical specifications and availability subject to change without notice Document ID A6V10336739_f_ _ SAP order no A5Q00048057 Manual FD20 DS11 1 Edition 2016 04 25 Section 5 4 ...

Reviews: