Replacement of coil

Fig. 3: Contactor – Relay Connection

Table A:

Motor  

Rating  

At 415V 3ph 50Hz

Starter Type

Relay 3UW51

Back-up Fuse Rating

Cu 

Cable 

(mm

2

size

Max. Full Load Current (Amp)

HP

kW

Range

Code 

##

HRC 

type 
3NA  

7

Rewirable

3Ph, 415V, 
4P Squirrel 

Cage IS 

8789:1996 

Table 4

3Ph, 415V, 

2P 

Submersible  

motor IS 

9283:1995 

Table 2

1Ph, 240V, 

CSIR or  

Split-Phase IS  

996-1979 

Table 9

0.33

0.25

3TW7291-1A* 64

0.63-1

0J

2A

36 SWG

1

3.8

0.75

0.55

3TW7291-1A* 66

1-1.6

1A

6A

34 SWG

1

1.7

7

1

0.75

3TW7291-1A* 68 

1.6-2.5

1C

6A

27 SWG

1

2.2

7

1.5 

1.1 

3TW7291-1A* 69

2-3.2

1D

10A

26 SWG

1

2.9

3.25

13

2

1.5

3TW7291-1A* 71

3.2-5

1F

16A

25 SWG

1

3.8

4.5

18

3

2.2

3TW7291-1A* 72

4-6.3

1G

16A

24 SWG

1.5

5.1

6.5

5

3.7

3TW7291-1A* 74 

6.3-10

1J

16A 

21 SWG

1.5

8.1

10

7.5

5.5 

3TW7291-1A* 75 

8-12.5

1K

25A 

19 SWG

1.5

11.4

14.5

7.5

5.5

3TW7291-1A* 77

10-16

2A

25A 

18 SWG

2.5

10

7.5

3TW7291-1A* 78 

12.5-20

2B

32A 

18 SWG

4

15.4

19.5

* Code for operating coil voltage, 50 Hz (B for 200-400V, W for 415V)

Spare list

Sr. 

No. 

Description

Order No.

1

Contactor for 200-400V

3TS30-10-0AZ608K

2

Contactor for 200-400V

3TS32-10-0AZ608K

3

Contactor for 415V

3TS30-10-0AR008K

4

Contactor for 415V

3TS32-10-0AR008K

Relay

3UW51 02-##

6   Coil for 200-400V

3TY7 403-0AZ6

7   Coil for 415V

3TY7 403-0AR0

8

1NO Contact Block

3SB54200B

9   ‘ON’ & ‘OFF’ Push Button

#

# – contact sales

Raja

+

 Direct-on-line Starter

(For Single Phase connection)

Wiring Diagram for Single-Phase Motors

Note: Connect 3/L2 to 2/T1 by cable of suitable size. (Max. 4mm

2

)

Hook on relay for 
engagement

Contactor 
outgoing terminals

Summary of Contents for DOL 3TW7291-1A

Page 1: ...ed Knob 6 Contactor Incoming Terminal Screws 7 Contactor Outgoing Terminal Screws 8 Contactor actuating green button 9 Wiring diagram Label 10 Links 11 Gasket 12 Grommet 13 Mounting Screw hole Fig 1 DOL Starter Fig 2 Starter Inside View Please read and understand these instructions before installating operating or maintaining the equipment Keep for future reference Danger Hazardous voltage can cau...

Page 2: ...on ON OFF Operation Rotate the Latch away from OFF push button Switch ON the starter by pressing the green push button marked I Fig 1 on the starter cover Switch OFF the starter by pressing the red push button marked O Fig 1 on the starter cover Reset Operation If the overload relay trips it resets automatically Allow a reset time of approx 4 min Maintenance Switch off the starter and disconnect t...

Page 3: ... 1G 16A 24 SWG 1 5 5 1 6 5 5 3 7 3TW7291 1A 74 6 3 10 1J 16A 21 SWG 1 5 8 1 10 7 5 5 5 3TW7291 1A 75 8 12 5 1K 25A 19 SWG 1 5 11 4 14 5 7 5 5 5 3TW7291 1A 77 10 16 2A 25A 18 SWG 2 5 10 7 5 3TW7291 1A 78 12 5 20 2B 32A 18 SWG 4 15 4 19 5 Code for operating coil voltage 50 Hz B for 200 400V W for 415V Spare list Sr No Description Order No 1 Contactor for 200 400V 3TS30 10 0AZ608K 2 Contactor for 200...

Page 4: ...als we recommend disassembling and separation into following materials METALS Segregate into Ferrous types for recycling through authorized dealer PLASTICS Segregate as per material type for recycling through authorized dealer Because of the long lifetime of Siemens Products the disposal guidelines may be replaced by other national regulations when taking the product out of service The local custo...

Reviews: