Siemens DLC Installation Instructions Manual Download Page 4

Siemens Industry, Inc.
Building Technologies  Division

P/N 315-033090-17

4

PRE-INSTALLATION

Set the three-digit HNET network address for the DLC using the three rotary dial
switches located near the bottom of the front panel. (Refer to Figure 1 for the
location of the switches.)  The address for the DLC must be the same as the address
selected for it in the Zeus Programming Tool. To set the address, turn the pointers on
each of the three dials to the numbers for the selected address. For example, if the
address is 123, set the pointer for the HUNDREDS dial to “1”, set the pointer for the
TENS dial to “2”, and set the pointer for the ONES dial to “3”.  The range of allowable
addresses is from 001 to 251 (leading zeros must be used).

INSTALLATION

The DLC plugs perpendicularly into one slot in the CC-5 card-cage via two 96-pin DIN
connectors and can occupy any slot in the card cage. (Refer to Figure 2.)

Insert the DLC card into the card guides rightside up
(lettering on the front panel is legible)

Slide the card in until the card edge connectors contact
the receptacles on the motherboard.

Verify that the DIN connectors of the card and the card-
cage are aligned properly. The card can only be plugged
into the card cage in one direction; if it does not align,
DO NOT FORCE the card.

Place thumbs on the front panel adjacent to the captive
screws and gently apply even pressure on the card until
the connectors seat in the receptacles on the
motherboard.

Secure the card with the captive screws.

WIRING

Remove all system power before installation, first battery then AC. (To power up,

connect the AC first, then the battery.)

All field wiring to the DLC is connected to the terminal blocks of the CC-5 card cage
slot in which it is installed.

To Connect External Wiring

1.

Loosen the screw of the terminal by turning it counterclockwise.

2.

Insert the wire into the side of the terminal block.

3.

Tighten the screw of the terminal block by turning it clockwise.

C24V from the PSC-12 to terminal 17 and -24V from the PSC-12 to terminal
18 of the slot in the CC-5 where the DLC will be installed. (Refer to Figure 3.)

Figure 2

Installing The  DLC

HNET

HUNDREDS

TENS

ONES

Summary of Contents for DLC

Page 1: ...ding on the loop The DLC communicates all relevant device and event information such as alarms and troubles to the System CPU The sensitivity of any intelligent smoke detector and the logic functions of any intelligent output devices can be checked and adjusted from the Operator Interface OI through the DLC All information about the devices on the loop can be displayed on the OI The DLC allows the...

Page 2: ...d indicates that the DLC has detected an alarm TROUBLE Yellow Normally OFF When illuminated indi cates that the DLC has detected a trouble on its field wiring or incapability between firmware in either the OI DLC or both Multi Criteria detectors Table 1 are supported by the OI FW version 9 02 and later and the DLC with Firmware version 06 xx and later The DLC can be made backwards compatible in sy...

Page 3: ...LASS A OPEN ZONE 2 Yellow Normally Off When illuminated indi cates a Zone 2 wire is open if the loop was set to Class A CLASS A RETURN ZONE 2 Yellow Normally Off When illuminated indi cates a Zone 2 return wire is reversed if the loop was set to Class A SHORT ZONE 2 Yellow Normally Off When illuminated indi cates a Zone 2 wire short Three rotary dial switches at the bottom of the front panel are u...

Page 4: ...el is legible Slide the card in until the card edge connectors contact the receptacles on the motherboard Verify that the DIN connectors of the card and the card cage are aligned properly The card can only be plugged into the card cage in one direction if it does not align DO NOT FORCE the card Place thumbs on the front panel adjacent to the captive screws and gently apply even pressure on the car...

Page 5: ...RUN OPERATES IN FULL CONFORMANCE WITH STYLE 6 ULC DCLA ZONE 1 ZONE 1 INITIATING DEVICE INITIATING DEVICE CC 5 CC 5 LINE 1 LINE 1 LINE 1 RETURN LINE 1 RETURN LINE 1 OUT LINE 1 OUT ZONE 2 ZONE 2 LINE 2 LINE 2 LINE 2 OUT LINE 2 OUT LINE 2 RETURN LINE 2 RETURN NOT USED NOT USED NOT USED NOT USED OPERATES IN FULL CONFORMANCE WITH STYLE 4 ULC DCLB SHIELD OPTIONAL TERMINATE IN ENCLOSURE WITH THE DLC TERM...

Page 6: ... not allowed on Class A loops 7 All models are UL and ULC listed 8 The Multi Criteria detectors are programmed using the DPU The SBGA 34 base connected to a ZIC 4A P N 500 033050 or ZIC 8B P N 500 648670 can be used to createTemporal 4 tones in conjunction with the Carbon Monoxide enabled detectors FDOOTC441 and OOHC941 Using these detectors with the ABHW 4S or ABHW 4B the selection of tones are c...

Page 7: ... 1 4 9 H O O 1 4 9 C H O O 1 2 9 P O C H L R W H L R 4 3 A G B S 7 8 5 5 0 4 0 1 V 6 A N P 7 8 5 5 0 4 0 1 V 6 A N P 8 8 5 5 0 4 0 1 V 6 A N P 9 5 6 5 9 0 5 1 3 N P 8 0 7 9 4 0 5 1 3 N P 0 1 2 3 3 0 5 1 3 N P 0 8 2 3 3 0 5 1 3 N P 3 9 1 4 9 0 5 1 3 N P 0 2 2 3 3 0 5 1 3 N P 6 6 8 6 3 3 0 1 V 6 A N P 6 6 8 6 3 3 0 1 V 6 A N P 2 6 6 4 2 3 0 1 V 6 A N P 6 2 9 3 2 3 0 1 V 6 A N P 5 5 6 4 2 3 0 1 V 6 A...

Page 8: ...180 220 80 240 210 70 200 60 180 50 170 170 230 40 160 160 220 190 100 30 150 Note 1 The total number of devices in two zones can not exceed 252 150 210 90 200 80 DLC LINE RESISTANCE vs MAX CURRENT LOAD OF DEVICES 190 70 140 Max Current Load of Devices Line Resistance Ohms 60 130 50 110 120 140 20 250 Note 2 The total current load in two zones cannot exceed 350ma Note 3 Max line resistance of each...

Page 9: ...eeds Such a security concept may result in additional site specific preven tive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...

Page 10: ...y Inc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada P N 315 033090 17 Siemens AG I BT FS SYS MCH D 81379 München Document ID A6V10239107 ...

Reviews: