Siemens DLC Installation Instructions Manual Download Page 1

Siemens 

Siemens 

Siemens 

Siemens 

Siemens Industry

Industry

Industry

Industry

Industry,,,,, Inc.

 Inc.

 Inc.

 Inc.

 Inc.

Building 

Building 

Building 

Building 

Building T

TT

TTec

ec

ec

ec

echnologies Di

hnologies Di

hnologies Di

hnologies Di

hnologies Division

vision

vision

vision

vision

P/N 315-033090-17

Device Loop Card

Installation Instructions
Model DLC

INTRODUCTION

The Model DLC Device Loop Card from Siemens Industry,
Inc., is the interface for connection of FireFinder-XLS/Desigo
Fire Safety Modular/Cerberus PRO Modular smoke detec-
tors, Multi-Criteria detectors including Carbon Monoxide,
manual stations, monitor devices, and control devices to the
FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO
Modular System. The DLC uses one network address on the
system. The application program that is loaded into the on-
board microprocessor controls the DLC operation.

The DLC contains 12 LEDs for diagnosis of problems.
Ground fault detection is provided by the loop.

All field devices connected to the DLC are addressed and
tested using the Device Programming Unit (DPU).

OPERATION

The DLC initializes, operates, and maintains all devices
residing on the loop. The DLC communicates all relevant
device and event information, such as alarms and troubles,
to the System CPU. The sensitivity of any intelligent smoke
detector and the logic functions of any intelligent output
devices can be checked and adjusted from the Operator
Interface (OI) through the DLC. All information about the
devices on the loop can be displayed on the OI. The DLC
allows the System polarity insensitive devices to be
connected without generating errors.

The DLC supports only one loop (two isolated parallel
zones) of up to 252 FireFinder-XLS/Desigo Fire Safety
Modular/Cerberus PRO Modular intelligent field devices as
well as device accessories (relay bases, audible bases, and
remote lamps) in any combination. The microprocessor
controls the on-board isolator to isolate either zone from
the loop if one of them is shorted. When one zone is
isolated from the loop, the other zone will still work.

The on-board microprocessor provides the DLC with the
ability to function and initiate alarm conditions even if the
main FireFinder-XLS/Desigo Fire Safety Modular/Cerberus
PRO Modular CPU fails.

DLC

ALARM

CLASS A OPEN

CLASS A RETURN

TROUBLE

SHORT

CARD FAIL

GND FAULT

HNET FAIL

RESET

Z

O
N

E

2

POWER

HNET

HUNDREDS

TENS

ONES

CLASS A OPEN

CLASS A RETURN

SHORT

ZONES STATUS

Z

O
N

E

1

Figure 1

DLC Device Loop Card

Summary of Contents for DLC

Page 1: ...ding on the loop The DLC communicates all relevant device and event information such as alarms and troubles to the System CPU The sensitivity of any intelligent smoke detector and the logic functions of any intelligent output devices can be checked and adjusted from the Operator Interface OI through the DLC All information about the devices on the loop can be displayed on the OI The DLC allows the...

Page 2: ...d indicates that the DLC has detected an alarm TROUBLE Yellow Normally OFF When illuminated indi cates that the DLC has detected a trouble on its field wiring or incapability between firmware in either the OI DLC or both Multi Criteria detectors Table 1 are supported by the OI FW version 9 02 and later and the DLC with Firmware version 06 xx and later The DLC can be made backwards compatible in sy...

Page 3: ...LASS A OPEN ZONE 2 Yellow Normally Off When illuminated indi cates a Zone 2 wire is open if the loop was set to Class A CLASS A RETURN ZONE 2 Yellow Normally Off When illuminated indi cates a Zone 2 return wire is reversed if the loop was set to Class A SHORT ZONE 2 Yellow Normally Off When illuminated indi cates a Zone 2 wire short Three rotary dial switches at the bottom of the front panel are u...

Page 4: ...el is legible Slide the card in until the card edge connectors contact the receptacles on the motherboard Verify that the DIN connectors of the card and the card cage are aligned properly The card can only be plugged into the card cage in one direction if it does not align DO NOT FORCE the card Place thumbs on the front panel adjacent to the captive screws and gently apply even pressure on the car...

Page 5: ...RUN OPERATES IN FULL CONFORMANCE WITH STYLE 6 ULC DCLA ZONE 1 ZONE 1 INITIATING DEVICE INITIATING DEVICE CC 5 CC 5 LINE 1 LINE 1 LINE 1 RETURN LINE 1 RETURN LINE 1 OUT LINE 1 OUT ZONE 2 ZONE 2 LINE 2 LINE 2 LINE 2 OUT LINE 2 OUT LINE 2 RETURN LINE 2 RETURN NOT USED NOT USED NOT USED NOT USED OPERATES IN FULL CONFORMANCE WITH STYLE 4 ULC DCLB SHIELD OPTIONAL TERMINATE IN ENCLOSURE WITH THE DLC TERM...

Page 6: ... not allowed on Class A loops 7 All models are UL and ULC listed 8 The Multi Criteria detectors are programmed using the DPU The SBGA 34 base connected to a ZIC 4A P N 500 033050 or ZIC 8B P N 500 648670 can be used to createTemporal 4 tones in conjunction with the Carbon Monoxide enabled detectors FDOOTC441 and OOHC941 Using these detectors with the ABHW 4S or ABHW 4B the selection of tones are c...

Page 7: ... 1 4 9 H O O 1 4 9 C H O O 1 2 9 P O C H L R W H L R 4 3 A G B S 7 8 5 5 0 4 0 1 V 6 A N P 7 8 5 5 0 4 0 1 V 6 A N P 8 8 5 5 0 4 0 1 V 6 A N P 9 5 6 5 9 0 5 1 3 N P 8 0 7 9 4 0 5 1 3 N P 0 1 2 3 3 0 5 1 3 N P 0 8 2 3 3 0 5 1 3 N P 3 9 1 4 9 0 5 1 3 N P 0 2 2 3 3 0 5 1 3 N P 6 6 8 6 3 3 0 1 V 6 A N P 6 6 8 6 3 3 0 1 V 6 A N P 2 6 6 4 2 3 0 1 V 6 A N P 6 2 9 3 2 3 0 1 V 6 A N P 5 5 6 4 2 3 0 1 V 6 A...

Page 8: ...180 220 80 240 210 70 200 60 180 50 170 170 230 40 160 160 220 190 100 30 150 Note 1 The total number of devices in two zones can not exceed 252 150 210 90 200 80 DLC LINE RESISTANCE vs MAX CURRENT LOAD OF DEVICES 190 70 140 Max Current Load of Devices Line Resistance Ohms 60 130 50 110 120 140 20 250 Note 2 The total current load in two zones cannot exceed 350ma Note 3 Max line resistance of each...

Page 9: ...eeds Such a security concept may result in additional site specific preven tive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...

Page 10: ...y Inc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada P N 315 033090 17 Siemens AG I BT FS SYS MCH D 81379 München Document ID A6V10239107 ...

Reviews: