Drivers, parameters, diagnostics messages and
address space
A
A.1
Parameter assignment
Parameter assignment in the user program
You can reconfigure individual channels of the module in RUN without this having an effect on
the other channels.
Changing parameters in RUN
The parameters are transferred to the module with the "WRREC" instruction via data record 128.
Output parameter STATUS
If errors occur when transferring parameters with the "WRREC" instruction, the module
continues operation with the previous parameter assignment. The STATUS output parameter
contains the corresponding error code.
The STATUS output parameter is 4 bytes long and is configured as followed:
• Byte1: Function_Num, general error code
• Byte2: Error_Decode, location of the error code
• Byte3: Error_Code_1, error code
• Byte4: Error_Code_2, manufacturer-specific extension of the error code
Module-specific errors are displayed via Error_Decode = 0x80 and Error_Code_1 / Error_Code_2.
Error_
Code_
1
Error_
Code_
2
Cause
Remedy
0xB0
0x00
Number of the data record unknown
Enter valid number for data record.
0xB1
0x01
Length of the data record is incorrect
Enter valid value for data record length.
0xB2
varia‐
ble
Module cannot be reached
• Check station - is the module plugged in cor‐
rectly?
• Check the parameters of the WRREC instruction.
0xE0
0x01
Wrong version in the header
Correct the version number of the parameter block.
0xE0
0x02
Header error (number or length of parameter block)
Correct the length and number of the parameter
blocks.
DI 16x24VDC HA
Equipment Manual, 10/2020, A5E39265608-AD
37
Summary of Contents for DI 16x24VDC HF
Page 6: ...Security information DI 16x24VDC HA 6 Equipment Manual 10 2020 A5E39265608 AD ...
Page 8: ...Preface DI 16x24VDC HA 8 Equipment Manual 10 2020 A5E39265608 AD ...
Page 10: ...2D Matrix code QR code EAN code DI 16x24VDC HA 10 Equipment Manual 10 2020 A5E39265608 AD ...
Page 36: ...Technical specifications DI 16x24VDC HA 36 Equipment Manual 10 2020 A5E39265608 AD ...