background image

Vehicle Description

Vehicle Function and Operational Interlocks
Type DHR vacuum circuit breakers are comprised of the
interrupter/operator module fitted to a vehicle.  This inter-
rupter/operator module is an integral arrangement of op-
erating mechanism, dielectric system, vacuum interrupt-
ers, and means of connecting the primary circuit.  The ve-
hicle supports the interrupter/operator module, providing
mobility and fully coordinated application in Westinghouse
type DH switchgear.

This manual should be used jointly with the Circuit Breaker
Operator manual, SGIM-9918.

Alignment
All aspects of the circuit breaker structure which impact
alignment and interchangeability are checked at the fac-
tory.  Field adjustment will not normally be required, but
variations in existing switchgear may require field adjust-
ment.

Recommended Tools

• Racking Crank: Original circuit breaker racking crank may

be used.

Installing Circuit Breaker Module Into Compartment

Note: CLOCKWISE ROTATION of racking for inserting
breaker. COUNTERCLOCKWISE ROTATION of racking
crank for removal of breaker.

Levering Device and Breaker Interlock
(Figure 1a and Figure 1b)
 shows the two extreme positions
of the of the levering device.

Levering-in Device
In order to move the breaker in or out of the metal clad cell
against the resistance of the contact fingers on the rear of
each bushing, a levering-in device is provided on each
breaker. There is an arm on each side mounted on a com-
mon shaft across the back of the breaker.  On each arm is
a roller which engages a groove in the sidewall of the cell.
A removable crank engages another shaft in the right front
corner of the breaker which turns the arms through a worm
gear and pinion arrangement.

Hazardous voltages and high-speed
moving parts. Will cause death, serious
injury, and property damage.

De-energize before working on this equip-
ment.

Do not by-pass interlocks or otherwise make
interlocks inoperative.

4

Before a breaker is rolled into a cell, the arms with rollers,
at each side of the breaker must point to the rear and slightly
downward as shown in (Figure 1a).  The arms travel 193
degrees and assume the horizontal position shown in (Fig-
ure 1b)
 when the breaker is cranked into the operating
position in the cell.  To put the arms in the position shown
in (Figure 1a), place the crank on the operating shaft at the
front right corner of the breaker (Figure 3) push in, and
rotate to engage the coupling in the levering-in device.  The
breaker contacts must be open to engage the coupling,
and the indicator will show “Interlocked”.  Rotate the crank
counterclockwise to the end of the travel.  During this time
the interlock mechanism will hold the coupling engaged.
At the end of the travel, the interlock will release, the crank
will move to the front, and the indicator on the mechanism
panel will point to the word “OPERATE”.

With the arms to the rear and down as shown in (Figure
1a)
, the breaker is ready to be rolled into the cell as far as

Figure 1a. Breaker out of the cell

Figure 1b. Breaker in the cell

Summary of Contents for DHR Series

Page 1: ...Instructions Installation Operation Maintenance SGIM 9958B Vacuum Circuit Breakers Vehicle Type DHR 4 16kV to 15kV ...

Page 2: ...rts should not be used in the repair of the equipment Follow all safety instructions contained herein IMPORTANT The information contained herein is general in nature and not intended for specific application purposes It does not relieve the user of responsibility to use sound practices in application installation operation and mainte nance of the equipment purchased Siemens reserves the right to m...

Page 3: ... Breaker Module Into Compartment 4 Levering Device and Breaker Interlock 4 Levering in Device 4 Interlock Position Indicator 5 Test Position 5 Operating Position 5 Interlock 5 Secondary Contacts 6 Ground Contact 6 Mechanism Operated Control Switch 6 Maintenance 7 Introduction and Maintenance Intervals 7 Recommended Maintenance and Lubrication 7 Removal from Switchgear 8 Checks of the Primary Power...

Page 4: ...ountered by the user These words are defined as Danger Indicates an imminently hazardous situation which if not avoided will result in death or serious in jury Warning Indicates a potentially hazardous situation which if not avoided could result in death or serious injury Caution indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury Dangerous Proce...

Page 5: ...e shipping pallet for later use if the breaker is to be stored prior to its installation 2 Inspect for concealed damage Notification to carrier must take place within 15 days to assure prompt reso lution of claims 3 Each circuit breaker should be appropriately lifted us ing lifting sling rated for at least 2 000 lbs Breaker shall be lifted by Upper B phase post insulator 4 The palleted circuit bre...

Page 6: ...re is an arm on each side mounted on a com mon shaft across the back of the breaker On each arm is a roller which engages a groove in the sidewall of the cell A removable crank engages another shaft in the right front corner of the breaker which turns the arms through a worm gear and pinion arrangement Hazardous voltages and high speed moving parts Will cause death serious injury and property dama...

Page 7: ...ce the inter lock is operative only when the breaker is in fan interme diate position between fully engaged and fully withdrawn it also serves as a means of indicating that the breaker is in the Operating Position and the main disconnecting con tacts fully engaged or that it is in the Test Position with the contacts separated Test Position The breaker may be rolled into the metal clad cell until t...

Page 8: ...ures a good electrical contact The flexible control wires are soldered to each plug and are arranged in a loop to allow free movement of the contact slide Figure 3 Secondary Contacts Ground Contact A ground contact is located at the left rear of the breaker from directly above the 18 point secondary plug Figure 3 Six spring loaded floating contact fingers engage the ground contact at the rear of t...

Page 9: ...sed on your experience with the equipment in the ac tual service environment Regardless of the length of the maintenance and lubrica tion interval Siemens recommends that circuit breakers and switchgear should be inspected and exercised annu ally Recommended Maintenance and Lubrication Periodic maintenance and lubrication should include all the tasks shown in Table 1 Recommended procedures for eac...

Page 10: ... red Trip pushbutton again and observe the spring con dition indicator It should read Discharge Refer to Cir cuit Breaker Operator Manual SGIM 9918 5 Remove the breaker from the switchgear Refer to the preceding installation section of this manual for special instructions and precautions regarding removal of a breaker which is not at floor level Checks of the Primary Power Path The primary power p...

Page 11: ...echanical damage burning or pitting Using a clean cloth saturated with denatured alcohol clean old lubricant from primary disconnects and apply Siemens contact lubricant reference 15 171 370 002 in a very thin layer Fastener Check Inspect all fasteners for tightness Both lock nuts and re taining rings are used Replace any fasteners that appear to have been frequently removed and replaced Racking M...

Page 12: ...9958B 1 2003 Printed in U S A 2001 Siemens Power Transmission Distribution Inc SIEMENS is a registered trademark of Siemens AG Siemens Power Transmission Distribution Inc P O Box 29503 Raleigh NC 27626 0503 ...

Reviews: