Building Technologies 

RXT20.1 – Service terminal 

CA2N3851en_02 / 12.01.2007 

 

 

 

3/6

 

 

If the service terminal is connected to a DESIGO RXB / RXC controller, the start-up rou-
tine is as follows: 

Step Display  Description 

 

All segments activated for approximately 5 s. 

 

Cursor fields may be activated for max. 10 s.* (approx.  
3 – 5 minutes * on controller power up, e.g. after operation of 
service pin) 

* Varies according to the DESIGO RX application 

 

Controller ready for operation (“run”

 

and cycling cursor) 

 

Display Description 

 

Normal operation between controller and room unit 

 

  Display reads “run” 

The room unit with the set address (see Address switch) communi-
cates with the controller. The “run” display can be overwritten by 
other displays (see  Additional information). 

  Cycling cursor, 1 s pulse 

The controller communicates (or tries to communicate). 

 

 

no communication, or controller not ready 

 

  Static display in all cursor fields 

There is no room unit connected or the controller is not ready for 
operation, but the power supply is working (controller in start-up 
phase, or no application loaded, or controller not configured). 

 

Faulty controller: 

 No display 

The power supply is not connected or the controller is faulty.  

 

Display Description 

 

Wink command

  

  Controller type displayed for 64 s (e.g. RXC30.1: “r.30”  

or RXB21.1: "r.21") 

Press the right key (Function key 2) to switch back to the original 
display before expiry of the 64 s. The display of the wink command 
takes priority over all other display options on the service terminal.  

The wink command can be used during commissioning to identify 
the currently addressed controller. 

 

RXC: see RXT10 user manual, document CA110338 

 

RXB: see ETS user manual  

 

Room temperature, operation mode  

  Room temperature in °C or °F (see "Function key 2") 

The displayed operation mode (Stand-by, Auto, fan speed) comes 
from the room unit. 

The same applies to the displayed room temperature, there is no tem-
perature sensor in the service terminal itself. 

LCD display

 

Response at start-up 

Additional information 

Summary of Contents for DESIGO RXT20.1

Page 1: ...gated or into the room unit of the controller concerned The service terminal displays the status of the controller and room unit the wink func tion error messages or additional information of the room unit The service pin of the connected DESIGO RXB RXC controller can be operated re motely with the function keys on the service terminal This function is especially useful for addressing controllers ...

Page 2: ...ess the controllers when commis sioning the system RXC refer to the RXT10 user manual document CA2110338 RXB refer to the ETS manual This function of the service terminal is especially useful for ad dressing controllers in concealed locations where direct access to the service pin is difficult For this purpose the service terminal is connected to the room unit of the controller concerned Press thi...

Page 3: ...ields There is no room unit connected or the controller is not ready for operation but the power supply is working controller in start up phase or no application loaded or controller not configured Faulty controller No display The power supply is not connected or the controller is faulty Display Description Wink command Controller type displayed for 64 s e g RXC30 1 r 30 or RXB21 1 r 21 Press the ...

Page 4: ... perature sensor of the connected room unit Display Description Room temperature in C or F see Function key 2 The displayed room temperature is the temperature measured by the room unit there is no temperature sensor in the service terminal itself The service terminal must have the same PPS2 address as the room unit address 1 12 in order to display any of the information described above The QAX3 r...

Page 5: ...able length Approx 15 cm Housing protection standard Protection standard to EN 60529 IP 30 Protection class Insulation protection class III Environmental conditions Operation IEC 721 Climatic conditions Class 3K5 Temperature 0 50 C Humidity 85 rh Mechanical conditions Class 3M1 Transport IEC 721 Climatic conditions Class 2K3 Temperature 25 70 C Humidity 95 rh Mechanical conditions Class 2M2 Indust...

Page 6: ...ommunicates with the controller via the PPS2 interface Addition ally the bus is looped through the service terminal RXC this enables a PC for the RXT10 service tool to be connected to the tool socket of the service terminal For correct operation of the service terminal there must always be a room unit connected to the controller PPS2 communication is not possible without a room unit 1 2 80443 A Au...

Reviews: