FNC Description of functions for FC-10, FC-11, FC-12
CM110385en_05
Building Technologies
Fan control
28 Feb 2009
Select
Fan control:
HandyTool
See Parameters in the last column of the table below
Parameter
Basic setting
Range
Resolution
HandyTool
Fan speed
3-speed
(see
below)
*094
Fan control
Auto Manual,
Auto
*093
Temperature sensor B1
Minimum on time
6 min
1 ... 10 min
1 min
*095
Fan overrun time
1 min
1 ... 10 min
1 min
*098
Periodic fan kick Comfort
OFF
0 ... 89 min ; Off
1 min
*096 1)
Periodic fan kick Economy
OFF
0 ... 359 min ; Off
1 min
*097 1)
1) HandyTool: 90 min / 360 min = OFF
9.2.1
Fan speeds and control
The following settings can be selected:
Parameter
Description
HandyTool
Fan speeds
*094
External
fan control
No influence on fans by controller or room unit.
The fan is e.g. operated manually at the fan coil.
The controller switches on relay Q14 in operating state
Comfort
, thus
allowing for enabling fan operation.
Note!
•
For safety reasons, this setting is not possible for applications with
electric heating coils or reheaters.
•
For other operating states but
Comfort
, the fan is enabled by the
fan algorithm.
0
1-speed
Single-speed fan control with relay Q14.
1
2-speed
Two-speed fan control with relays Q14 and Q24.
2
3-speed
Three-speed fan control with relays Q14, Q24 and Q34.
3
ACS
Service
9.2.1
9.2.2
7.1.2
9.2.4
9.2.3