54/166
Siemens
RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12
CM110385en_05
Building Technologies
Room operating modes
28 Feb 2009
The table below shows the effect of the
Temporary Comfort mode
on the
effective room
operating mode
of the room controller.
Existing effective
room op. mode
Temporary
Comfort mode
New effective
room
operating mode
Comfort
Æ
0 = Not used
No effect
Precomfort
Æ
1 = Trigger
Comfort
Economy
Æ
1 = Trigger
Comfort
during
Temporary
Comfort
mode
1)
Protection mode
Æ
1 = Trigger
Protection
, no change
Key:
Æ
1 means: "changes to 1"
1)
Comfort
mode is operative for the pre-defined
Temporary Comfort
period (see
page 126). The room controller then reverts to
Economy.
5.4.7
Effective room operating mode
PPS2
S
Central
Local
1.
3.
S
DI
S
S
DI
3.
Controller
1.
3.
Prio
3.
S
S
For the building automation and control system the
resulting
effective room operating mode
is available to
the building automation and control system as follows:
Effective room operating mode (Output communication object)
Flags
R
W
C
T
U
Type
Send heartbeat
States
1 0 1 1 0 20.102
DPT_HVACMode
Yes
1 = Comfort
2 = Precomfort
3 = Economy
4 = Protection
The resultant
Effective room operating mode
is also available as 4 digital
communication objects:
Effective room operating mode Comfort (output communication object)
Effective room operating mode Precomfort (output communication object)
Effective room operating mode Economy (output communication object)
Effective room operating mode Protection (output communication object)
Flags
R W C T U
Type Send
heartbeat
States
1 0 1 1 0 1.001
DPT_Switch
Yes
0 = Off
1 = On