11.2 Digital inputs
The following volt-free contacts can be connected to digital inputs D1 and D2:
•
Presence detector or window contact (for details of this function see Section 5).
•
Safety thermostat electric heating coil / reheater (for details of this function, see
page 95).
•
Safety thermostat outdoor temperature (for details of this function, see page 103).
Digital input
Function
Type of operation
HandyTool
Input 1
Input 2
*113
*114
Not used by the
application
Free: Bus = 1
= Contact closed
Free: Bus = 1
= Contact open
0= Default
1
(Contact may be used freely (see page 136 )
Occupancy
Occupied
= Contact closed
Occupied
= Contact open
3
2
Window
Window open
= Contact open
Window open
= Contact closed
4
5
Safety thermostat
el. heating coil
Overtemp
= Contact closed
Overtemp
= Contact open
16
17
Safety thermostat
Outside temperature
OT < frost
= Contact closed
OT < frost
= Contact open
(applications with outside air damper only)
33
32
Do not connect the same type of sensor/functions to both digital inputs.
The controller would ignore the second input.
11.3 Temporary Comfort mode
If the room controller is set to
Economy
mode and the associated room unit is switched
to Auto
(Comfort)
, the controller maintains
Comfort
mode for the period defined by the
temporary occupancy override time (veto) and then switches to
Economy.
This function
is only available if the room unit concerned has a /Auto switch (see also pages 42
and 53).
Parameter
Basic
setting
Range
Resolution
HandyTool
Temporary Comfort mode
60 min
0 ... 360 min 1 min
*117
11.4 Presence detector switch-on and
switch-off delay
A switch-on or switch-off delay can be applied to the presence detector function. The
room controller only switches to
Comfort
or to
Precomfort
or
Economy
mode when the
delay time has expired.
Parameter
Basic
setting
Range
Resolution
HandyTool
On delay occupancy detector
5 min
0 ... 90 min
1 min
*119
Off-delay occupancy detector
5 min
0 ... 90 min
1 min
*120
Note