120/140
Siemens
RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
KNX information
28 Feb 2009
12.5.2 S-mode output communication objects
Flags:
R
Read
T
Transmit
W
Write
U
Update
-C
Communication
1)
C.S. = Company specific
For internal use only
Name
Flags:
Data point type (KONNEX)
Send
See
R W C T U
heartbeat
page
Alarm info
1 0 1 1 0 219.001 DPT_AlarmInfo
Yes
Analog input B1
1 0 1 1 0 9.001
DPT_Value_Temp
Ja
Common alarm
1 0 1 1 0 1.005
DPT_Alarm
Yes
Cooling surface output
1 0 1 1 0 5.001
DPT_Scaling
Digital input 1
1 0 1 1 0 1.001
DPT_Switch
No
Digital input 2
1 0 1 1 0 1.001
DPT_Switch
No
Heating surface output
1 0 1 1 0 5.001
DPT_Scaling
Yes
Effective application mode
1 0 1 1 0 20.105 DPT_HVACContrMode
Yes
Effective occupancy
1 0 1 1 0 20.003 DPT_OccMode
Yes
Effective room operating mode
1 0 1 1 0 20.102 DPT_HVACMode
Yes
Effective room operating mode
Comfort
1 0 1 1 0 1.001
DPT_Switch
Yes
Effective room operating mode
Economy
1 0 1 1 0 1.001
DPT_Switch
Yes
Effective room operating mode
Precomfort
1 0 1 1 0 1.001
DPT_Switch
Yes
Effective room operating mode
Protection
1 0 1 1 0 1.001
DPT_Switch
Yes
Effective room temperature
1 0 1 1 0 9.001
DPT_Value_Temp
Yes
Effective setpoint
1 0 1 1 0 9.001
DPT_Value_Temp
Yes
Effective setpoint heating
1 0 1 1 0 9.001
DPT_Value_Temp
Yes
Effective setpoint cooling
1 0 1 1 0 9.001
DPT_Value_Temp
Yes
Effective setpoint offset
1 0 1 1 0 9.002
DPT_Value_Tempd
Yes
Energy demand room
1 0 1 1 0 6.001
DPT_Percent_V8
Yes
Master/slave HVAC controller
output
1 0 1 1 0 C.S.
1)
13
Byte
Yes
Master/slave room unit output
1 0 1 1 0 C.S.
1)
4
Byte
Yes
Presence detector output
1 0 1 1 0 1.018
DPT_Occupancy
Yes
Present setpoint ...
1 0 1 1 0 9.001
DPT_Value_Temp
Yes
Present setpoint ...
(6 indiv. values)
1 0 1 1 0 9.001
DPT_Value_Temp
Yes
Present setpoints cooling
1 0 1 1 0 222.100 DPT_TempRoomSetpSetF16[3] Yes
Present setpoints heating
1 0 1 1 0 222.100 DPT_TempRoomSetpSetF16[3] Yes
Room dewpoint alarm output
1 0 1 1 0 1.005
DPT_Alarm
Yes
Room temperature output
1 0 1 1 0 9.001
DPT_Value_Temp
Yes
Status
1 0 1 1 0 C.S.
1)
2
Byte
No
Window switch output
1 0 1 1 0 1.019
DPT_Window_Door
Yes