Temperature measurement
28 Feb 2009
7.1.5
Temperature sensor outputs on the Konnex bus
To map the local temperature measurement in a building automation and control
system, the following two output communication objects are used:
RXB... Room controller
10384Z15en
Effective room temperature
Room temperature output
R
O
+
The value of the communication object
Room temperature output
is not filtered (not
smoothed).
Sending takes place only if room "Room" is parameterized for the temperature sensor
B1.
The value transmitted as the
Effective room Temperature
is the filtered (smoothed)
value of the communication object
Room temperature output
or
Return air temperature
output,
Room temperature output (output communication object)
Effective room temperature (output communication object)
Flags
R W C T U
Type
Send heartbeat
Value
1 0 1 1 0 9.001
DPT_Value_Temp
Yes
Floating point (°C)
Invalid temperatures are mapped to the bus as 0 °C.
In LTE mode, the room air temperature from directly connected sensors is mapped as
follows:
Room temperature output (output)
Possible partner function
blocks)
Known partner devices
TempRoom 390
UHD
UserHVACDisplay
Siemens:
Synco RMH760 / RMB795
RMU710 / 20 / 30
Geographical zone
Note