Building Technologies
Temperature measurement
28 Feb 2009
Select tab
General functions, Temperature sensor B1
Select
General functions, Temperature sensor r B1
HandyTool
See the parameters in the last column of the following table.
Short name
Basic setting
Parameter
Temperature sensor B1
No sensor
*092
Room
1
Only meas val acquisition
3
No sensor
255
Only meas val acquisition: Use of the signal: see "analog input B1", page 112.
7.1.3
Averaging analog input & PPS2 interface
In large spaces it can be useful to measure the room temperature in two locations and
to determine an average value. If both a QAX3… room unit and a QAA24 LG-Ni1000
sensor are connected to a controller, the measured room temperature is automatically
based on the average value from both sensors. Automatic detection prevents
miscalculation.
A QAX34 / QAX84 will display this average value.
PPS2 (CP+, CP-)
B1
QAX3...
RXB2...
QAA24
103
8
5Z
1
4
The average value is calculated from the two sensor readings.
•
To determine the average value, the sensor must be configured as a room
temperature sensor
•
There is no averaging in KNX sensors.
7.1.4
Sensor correction
The value of the local sensors (PPS2 and B1) can be corrected in the tools
(see page 115).
ETS3
Professional
ACS
Service
Notes