Document No. 565-718
Installation Instructions
December 15, 2009
Connecting the CSI Host Driver to
the CSI System
Follow these steps to connect the CSI Host Driver
to the CSI system:
1. Make cables per diagram in Figure 1 or Figure 2.
2. Install the Trunk Interface II per diagram in
Figure 1 or Figure 2.
3. Connect cables per diagram in Figure 1 or
Figure 2.
4. Plug in the power supply for the Trunk Interface II
per diagram in Figure 1 or Figure 2.
FLN
DRIVER
S
-
+
EACH FLN CONNECTOR REQUIRES
RS-485 TRUNK CABLE (MAX 4000 ft/1200 m;
STANDARD 24 AWG LOW CAPACITANCE)
GROUND WIRE TO EARTH
(P/N 538-583)
POWER PACK
TRUNK INTERFACE II
GW1173R3
RS-232 PORT
(25-PIN FEMALE)
RS-232 PORT
(9-PIN MALE)
POWER
TAPE BACK
SHIELD
FLN
S
-
+
IF DRIVER
IS LESS THAN
50 CABLE FEET
(15 m)
FROM CSI PANEL
PLACE THE TRUNK
INTERFACE II
IN THE MBC
ENCLOSURE
2 3 7
2 3 5
25-PIN MALE TO 9-PIN FEMALE
(P/N 536-004)
CSI DCU or
PCU Controller
with RS-232 Port
CABLE:
Figure 1.
Connecting the Driver to the CSI System (Recommended).
Page 2 of 4