5.3.2.1 Technical Data
Voltage input
(voltage is provided via terminals)
PS-8620
PS-8622
Input voltage
DC 24…60 V
DC 110…220 V
Operating voltage
DC 18…70 V (78 V
1)
)
DC 82.5…253 V (286 V
1)
)
Input current
0.8 A at DC 24 V
0.4 A at DC 48 V
0.3 A at DC 60 V
0.16 A at DC 110 V
0.08 A at DC 220 V
Reverse voltage protection
Yes
Overload protection
Yes
Short-circuit protection
Yes
Can be connected in parallel
Yes (for redundancy, not for power enhancement)
1)
Inrush peak current
Specified acc. to IEC 60870-4 (90) class S1
Voltage outputs
Output nominal voltage 1
DC 5.15 V ± 2% static, ±3% dynamic
Output nominal current 1
0…1.8 A
Output nominal voltage 2
DC 28 V ±10%static, ±3% dynamic
2)
Output nominal current 2
0…0.43 A
Output power 1 (P
out 1
)
9 W
Output power 2 (P
out 2
)
12 W - P
out 1
(12 W if P
out 1
= 0 W)
Total output power
12 W
Guaranteed interruption time
50 ms
Startup time
< 2 s
Permanent short-circuit proof
Yes
Mechanics
Connections
Removable screw terminals, 4-pole (grid size 5.08)
wire cross sections up to 2.5 mm²
Dimension (LxWxH)
124 x 30 x 132 mm (measure without DIN rail)
Weight
Approx. 240 g (incl. bus module 12 g)
1)
as of production level CC
2)
for the generation of the auxiliary voltage for specific transmission facilities