2.1.4
I/O
Master
Module
The virtual I/O Master Module serves for the acquisition or output of process signals and per-
forms the process-compliant adaptation, monitoring and processing of the process signals at
each point of entrance or exit of the system. Its functionality is provided by means of a
loadable and parameter-settable firmware.
Features
•
Support of I/O Modules
─
CP-8000: 2 internal and up to 6 external I/O Modules (maximal 116 I/Os)
─
CP-802
x
: up to 8 external I/O Modules (maximal 128 I/Os)
•
Acquisition and preprocessing of process data according to IEC 60870-5-101/104 with and
without time tag
─
Transmission of process information to the
telecontrol function
(for further distribution)
and to the
open-/closed-loop control function
(for further processing)
−
Single-point and double-point information items
−
Count pulses
−
Measured values
─
Transmission of system information (example: diagnosis data)
•
Postprocessing and output of process data according to IEC 60870-5-101/104
─
Reception of process information from the
telecontrol function
and from the
open-/closed-
loop control function
−
Single-point information items
−
Single-point and double-point commands
−
Setpoint commands
─
Reception of system information (example: parameters)
•
Test functions for process signals
•
Secured data exchange with the I/O Modules
•
Supervision of the I/O Modules and failure handling
•
Status for process signals via display (CP-8000 only)
•
Error display via LED
Product Overview
Type
Designation
USIO80
Firmware
Universal Signal Input and Output
for the connection of
SICAM TM I/O Modules (only with CP-8000)
USIO81
Firmware
Universal Signal Input and Output
for the connection of
SICAM I/O Modules
Summary of Contents for CP-8000