Installation and Circuitry
212
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
6.11
Installation of External Communication Connections
Via the communication interfaces of CP-8000/CP-802
x
selected transmission facilities can be
connected. Depending on the kind of the selected communication type, different connection
cables are required for the connection of a data transmission facility.
Connection type
Communication type
Transmission Facility
Connection cable
Serial
Multi-point traffic
•
Leased line modem
•
VFT channel modem
Modem cable
See section
Multi-point traffic via
glass fiber optic
Optional star coupler
D-sub/RJ45 adapter
See section
Dial-up traffic analog
Westermo TD-36, TDW-33
with external supply
See section
Dial-up traffic ISDN
Westermo IDW -90 with
external supply
See section
Dial-up traffic GSM
Cinterion MC52iT
See section
SMS
MC Technologies MC55iw
See section
Point-to-point traffic
–
See section
Ethernet TCP/IP
LAN/WAN
Patch cable
GPRS
•
Internal (CP-8022)
•
M874-2 GPRS Modem
•
MD741-1 GPRS Router
Patch cable
Patch cable
Order information for transmission facilities and cables see appendix
and
,
Note
Communication cables are, if possible, to be installed separately from the supply and peripheral cables.
Caution
It is not permitted to connect a serial port with an Ethernet interface and vice versa.
Note
With a serial connection via X2 a bridge between CTS and GND is required, as far as the interface shall
also be used for the connection with the engineering PC.
By means of a special parameter you can define that the interface X2 is not used for engineering
(
Communication settings serial | Serial engineering interface
=
disabled
).
Thereby the connection between CTS and GND is not required.