Installation and Circuitry
196
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
6.7
Wiring
Due to the power dissipation in the device there is a higher temperature on the terminals than
the device ambient temperature. This increase is maximum 15°K with full load. For this reason
the isolation of the wires must withstand a higher temperature than the device environment
temperature (see example for
6.7.1 Power
Supply
CP-8000 has an integrated power supply module (see
•
The supply can be performed via a station battery or series power units.
•
For the fuse protection a circuit breaker 2-pole 2 A, characteristic C is prescribed (stand-
ard type: Siemens 5SY5 202-7).
CP-802
x
needs an external power supply module PS-862
x
or PS-864
x
(see
,
,
).
•
The supply can be performed via a station battery or series power units.
•
PS-8642 can be supplied optionally via the public low-voltage network.
•
Furthermore, 2 redundant power supply modules can be used (PS-862
x
as of production
level CC).
•
For the fuse protection of PS-862
x
a circuit breaker 2-pole with 2 A, characteristic C is
prescribed (standard type: Siemens 5SY5 202-7).
•
For the fuse protection of PS-864
x
a circuit breaker 2-pole with 10 A, characteristic C is
prescribed (standard type: Siemens 5SY5 210-7).
You can establish the supply with single leads of the type H07V-K (1.5…2.5 mm²) or a cable
of the type LA-YY-0 (2 x 1.5…2.5 mm²) or H05VV-F 3G (1.5…2.5 mm²).
Recommended and tested series power units (standard types) can be found in the Appendix
,
Recommended Upstream Power Supply Devices
6.7.2 Communication
RS-485
The wiring at the RS-485 interface is specified as follows:
Max. ambient temperature
min.
max.
Conductor cross section solid
0.2 mm²
1.5 mm²
Conductor cross section flexible
0.2 mm²
1.5 mm²
Conductor cross section flexible, with ferrule w/o plastic sleeve
0.25 mm²
1.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve
0.25 mm²
0.75 mm²
Conductor cross section AWG
24
16
AWG according to UL/CUL
16
24
Summary of Contents for CP-8000