System Components and Technical Data
150
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
5.7.2.3 AI-8310
5.7.2.3.1 Functions
•
Temperatures
t1
─
Connecting resistance thermometers: 2-, 3- or 4-wire technique
─
Settable measuring ranges
−
Temperature values
Input range
Pt100: -50…+350°C / -58…+662°F / (
≈
80.31…229.67
Ω
)
Pt100: -100…+700°C / -148…+1292°F / (
≈
60.25…345.13
Ω
)
Ni100: -60…+250°C / -76…+482°F / (
≈
69.5…289.2
Ω
)
Pt1000: -100…+700°C / -148…+1292°F / (
≈
602.5…3451.3
Ω
)
Resolution
Pt100: -50…+350°C 0.15°C / 0.28°F / (10 m
Ω
)
Pt100: -100…+700°C 0.15°C / 0.28°F / (10 m
Ω
)
Ni100: -60…+250°C 0.15°C / 0.28°F / (10 m
Ω
)
Pt1000: -100…+700°C 0,15°C / 0,28°F / (100 m
Ω
)
Response time
16
⅔
Hz < 1.2 s
50 Hz < 1.0 s
60 Hz < 0.9 s
−
Resistance values
Input range
40…400
Ω
, Resolution: 10 m
Ω
400…4000
Ω
, Resolution: 100 m
Ω
Response time
16
⅔
Hz < 1.2 s
50 Hz < 1.0 s
60 Hz < 0.9 s
─
Revision
─
Noise rejection
─
Calibration for 2-wire technique
─
Smoothing
─
Adaption
−
Temperature value (°C, °F), conversion using implemented curves
−
Resistance value (
Ω
)
─
Change monitoring
─
Spontaneous transmission upon change
Summary of Contents for CP-8000