background image

2

OPERATION

External Output Loading

It is critical that sufficient battery energy be provided for

either  24  hour  or  60  hour  system  operation. All  circuit

loading is fixed except for the following (See the 

CON-

NECTION DIAGRAM 

on pages 4-5, also).

1. Class B Supervised General Alarm Audibles

TB2, terminals 1 and 2

Rated 24 VDC, 1.5A max

2. Class B Supervised Discharge Audibles

TB2, terminals 3 and 4

Rated 24 VDC, 1.5A max

3. Class B Supervised Discharge Circuit

TB2, terminals 5 and 6

Rated 24 VDC, 2.0A max

The table below provides a listing of the various visual indi-

cators provided within the CP-2ER Control Panel unit. The

labels appearing on the unit are printed in capital letters.

SERVICE SELECTION Jumper

The 

SERVICE SELECTION 

jumper is provided so that a

CP-2ER system can be operated under NFPA 72 Local or

NFPA 12A, 13 or 2001.

  For NFPA 72 Local Service:

• Do not place 

SERVICE SELECTION 

plug in P12 po-

sition.

NOTE:

Plug may be either in P72 or not used

for 72 Local service.

• Connect 5.6K ohm, 1/2W, end-of-line resistor across

TB2, terminals 3 and 4.

• Connect 1K ohm, 1W, end-of-line resistor across TB2,

terminals 5 and 6.

Initiating Circuit and Local Protective Signaling Panel

Operation 

(Selection Plug Placed on P72).

A single zone alarm results in the following:

1. An alarm lock-in of that zone.

2. A visual alarm condition of that zone.

3. A general alarm condition of the panel which includes:

a. Change of state of fire alarm relay contacts (TB3,

terminals 4 through 9).

b. General alarm audible circuit actuated.

Since  neither  the  discharge  audible  circuit  nor  the  dis-

charge device circuit is used, an initiation of the second

zone  results  in  only  a  visual  display  indicating  that  the

second zone has alarmed.

VISUAL INDICATORS

COLOR

Visual Indicators Externally Visible

•

POWER

— Steady on indicates main power is normal.

Green

— Flashing on/off indicates panel is operating from the backup battery supply.

• System 

TROUBLE 

—

 

Indicates a general system trouble.

Yellow

• System 

SUPERVISORY

 — Indicates a general system supervisory

Yellow

•

ALARM ZONE 1

Red

•

ALARM ZONE 2

Red

• Predischarge/DISCHARGE alarm operates in flashing mode upon cross zone

Red

(Zone 1 and Zone 2) activation condition until preselected time delay has expired.

Operates in steady mode upon, and following, actual discharge.

• Audible 

ALARM SILENCED 

indicates that either the general alarm audible

Red

   device or predischarge/discharge audible device circuit has been silenced.

Visual Indicators Internally Visible (Must open panel door to be viewed)

•

BATTERY FAULT 

indicates high/low (or open) battery fault condition or open battery circuit.

Yellow

•

GROUND FAULT

Yellow

•

Abort station circuit fault 

(ABORT TROUBLE)

Yellow

•

Manual release station circuit fault 

(MANUAL DISCHARGE TROUBLE)

Yellow

•

Release circuit fault 

(AGENT DISCHARGE TROUBLE)

Yellow

•

Zone 1 initiation circuit fault 

(ZONE 1 TROUBLE)

Yellow

•

Zone 2 initiation circuit fault 

(ZONE 2 TROUBLE)

Yellow

• General alarm audible circuit fault 

(GENERAL ALARM TROUBLE)

Yellow

•

Predischarge/discharge audible alarm circuit fault 

(PREDISCHARGE TROUBLE)

Yellow

•

CYLINDER PRESSURE TROUBLE

Yellow

•

CYLINDER PRESSURE SUPERVISORY

Yellow

•

BATTERY CHARGER 

Charging current operation

Light Red

Internally Operated Switch Functions

• System 

RESET/LAMP TEST 

switch (momentary)

• Audible 

ALARM SILENCE 

switch (momentary)

• System audible 

SUPERVISORY SILENCE 

switch

•

System audible 

TROUBLE SILENCE 

switch

•

RELEASE DISCONNECT

 switch

Technical Manuals Online! - http://www.tech-man.com

Summary of Contents for CP-2ER

Page 1: ...g Technologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN Fire Safety Siemens Building Technologies Inc 8 Fernwood Road Florham Park New Jersey 07932 SUPERVISORY TROUBLE ALARM ZONE 1 DISCHARGE ALARM SILENCED ALARM ZONE 2 POWER ON BATTERY WHEN FLASHING Technical Manuals Online http www tech man com ...

Page 2: ... Contents INTRODUCTION 1 OPERATION 2 CONNECTION DIAGRAM 4 5 INSTALLATION AND WIRING 7 POWER LIMITED WIRING 8 MAINTENANCE AND TESTING 9 TROUBLESHOOTING THE SYSTEM 9 Technical Manuals Online http www tech man com ...

Page 3: ...t ing zone causes the general alarm to sound again To set the CP 2ER to meet NFPA 12A 13 or 2001 require ments for a releasing panel place the SERVICE SELEC TION plug in position P12 Release With the plug in this position both a general alarm associated with the first ini tiating zone actuation and a predischarge discharge alarm with actuation of the second initiating zone will sound The position ...

Page 4: ...econd zone results in only a visual display indicating that the second zone has alarmed VISUAL INDICATORS COLOR Visual Indicators Externally Visible POWER Steady on indicates main power is normal Green Flashing on off indicates panel is operating from the backup battery supply System TROUBLE Indicates a general system trouble Yellow System SUPERVISORY Indicates a general system supervisory Yellow ...

Page 5: ...d position during a non discharge or circuit activation condition causes an open circuit trouble indication of the release circuit This prevents the associated dis charge devices from activating If the ALARM SILENCE switch has been operated after initiation of the first zone alarm a second zone alarm re sults in reactivating the general alarm audible circuit which may then be silenced again For NF...

Page 6: ...STATION MODEL AW 1 N O CYLINDER SUPERVISORY SWITCH P N 500 878709 MANUAL DISCHARGE PRESSURE SWITCH P N 500 486536 5 6K 1 2W EOL W 2 2K 1 2W EOL W 3 2 1 POWER SUPPLY P1 INPUT 120V 50 60 HZ 2A MAX NEUTRAL P2 BATTERIES 24 VDC Charging Current Normal 300mA 24 VDC Charging Current Max 560mA Load Current Max 3 3A 4 0A with self interrupting solenoid P N 500 890181 24 HR P N 175 084476 5 AH 60 HR P N 175...

Page 7: ... Service 7 Refer to OPERATING INSTRUCTIONS P N 315 193524 8 To use power limited wiring to NFPA 70 NEC the audible circuits terminals 1 4 of TB2 must use the PLM 35 module Refer to In structions P N 315 093495 Initiating circuits TB1 terminals 1 14 are power limited as they are 9 For a list of COMPATIBLE NOTIFICATION APPLIANCES refer to P N 315 096363 DESIGNATION RATING CIRCUIT F1 F2 F3 F4 5A 2A 2...

Page 8: ...he delay period when the agent is re leased the discharge audibles sound in a steady manner b If the ABORT switch is depressed before the 30 second time in period ends 1 The discharge audibles are silenced during the 90 second abort duration period NOTE The 90 second delay period associated with the external abort switch is provided by others 5 Switch S101 Dial setting Rotate to change setting Dia...

Page 9: ...eration without first consulting one of the above Mounting Control Units Refer to Figure 2 Securely fasten the control unit to a shock and vibration free surface in a clean dry area It must be mounted far ther than 3 feet but less than 6 feet from the floor The location should be easily visible readily accessible for main tenance and should allow sufficient clearance to open the hinged front door ...

Page 10: ...ice is requested 15 days prior to the tests so that the services of the technician may be scheduled The installation of the wiring should be checked as follows 1 Detectors should not be in their bases Temporary jump ers should be inserted in all bases if not already in stalled Install end of line resistor to appropriate termi nals of last detector on circuit for Class B wiring For Class A wiring i...

Page 11: ...2 PLM 35 If the PLM 35 module is required mount it on the left side wall of the enclosure as shown in Figure 3 Refer to PLM 35 Installation Instructions P N 315 093495 MAINTENANCE AND TESTING To insure proper and reliable operation refer to NFPA 72 Local 12A or 2001 as appropriate for applicable main tenance and testing schedule and instructions CAUTION Make sure that release circuits and shunt tr...

Page 12: ... wiring Zone 1 and or Zone 2 initiating circuits TB1 between terminals 2 and 3 or between terminals 6 and 7 open circuited or not terminated with a 1 78K ohm resistor Wiring resistance between terminals 1 and 2 3 and 4 5 and 6 or 7 and 8 exceeds acceptable limits Refer to CONNECTION DIAGRAM on pages 4 5 7 General alarm audible alarm circuit TB2 terminals 1 and 2 open circuited or not termi nated w...

Reviews: