Issue 03/01
5 System Parameters
MICROMASTER 411 & COMBIMASTER 411 Operating Instructions
6SE6400-5CA00-0BP0
71
ParNr ParText
Default
Acc
WS
QC
r0208
Rated inverter voltage
-
2
-
-
r0209
Maximum inverter current
-
2
-
-
P0210 Supply
voltage
230 3 CT
N
P0290
Inverter overload reaction
2
3
CT
N
P0292
Inverter overload warning
5
3
CUT
N
P1800 Pulse
frequency
4 2 CUT
N
r1801
CO: Act. pulse frequency
-
3
-
-
P1802 Modulator
mode
0 3 CUT
N
P1820[1]
Reverse output phase sequence
0
2
CT
N
Motor data (P0004 = 3)
ParNr ParText
Default
Acc
WS
QC
r0034[1]
CO: Motor temperature (i2t)
-
2
-
-
P0300[1]
Select motor type
1
2
C
Q
P0304[1]
Rated motor voltage
230
1
C
Q
P0305[1]
Rated motor current
3.25
1
C
Q
P0307[1]
Rated motor power
0.75
1
C
Q
P0308[1]
Rated motor cosPhi
0.000
2
C
Q
P0309[1]
Rated motor efficiency
0.0
2
C
Q
P0310[1]
Rated motor frequency
50.00
1
C
Q
P0311[1]
Rated motor speed
0
1
C
Q
r0313[1]
Motor pole pairs
-
3
-
-
P0320[1]
Motor magnetizing current
0.0
3
CT
Q
r0330[1]
Rated motor slip
-
3
-
-
r0331[1]
Rated magnetization current
-
3
-
-
r0332[1]
Rated power factor
-
3
-
-
P0335[1] Motor
cooling
0
2 CT Q
P0340[1]
Calculation of motor parameters
0
2
CT
N
P0344[1] Motor
weight
9.4 3 CUT
N
P0346[1] Magnetization
time
1.000 3 CUT
N
P0347[1] Demagnetization
time
1.000 3 CUT
N
P0350[1]
Stator resistance (line-to-line)
4.00000
2
CUT
N
r0384[1]
Rotor time constant
-
3
-
-
r0395
CO: Total stator resistance [%]
-
3
-
-
P0399
Motor mirror mode
2
3
CT
N
P0610[1]
Motor I2t temperature reaction
2
3
CT
N
P0611[1]
Motor I2t time constant
100
2
CT
N
P0614[1]
Motor I2t overload warning level
100.0
2
CUT
N
P0640[1]
Motor overload factor [%]
150.0
2
CUT
Q
P1910
Select motor data identification
0
2
CT
Q
r1912[1]
Identified stator resistance
-
2
-
-