COM32 INSTALLATION & OPERATION MANUAL
17
Technical Specifications
4
Technical Specifications
N
OTE
RS-485 port terminals all pass ANSI/IEEE C37.90A-1989 surge withstand and fast transient tests.
Electrical Ratings
Isolation:
500 V between RS-232 and RS-485 ports
Power Supply:
Standard 9VDC @ 500 mA
(120 VAC adapter supplied)
Alternate: 9 VDC @ 500 mA
(220 VAC adapter)
Operating Temperature:
0
°
C to 50
°
C (32
°
F to 122
°
F) ambient air
Storage Temperature:
-30
°
C to 70
°
C (-22
°
F to 158
°
F)
Humidity:
5 to 95 percent, non-condensing
Shipping Weight:
COM32: 0.24 kg; 8 oz.
COM32 with standard power supply: 0.47 kg; 1lb.
COM32 with alternate power supply: 0.63 kg; 1 lb. 6 oz.
Shipping Carton:
30 cm x 25 cm x 15 cm
(11.8” x 9.8” x 5.9”)
Features
Baud Rates Supported:
1200, 2400, 4800, 9600
RS-232 Ports:
One (Female DB-25)
RS-485 Ports:
One screw-down terminal blocks, each with (+), (-), and shield (SHLD)
terminals
Summary of Contents for COM32