Siemens CLM0C Installation Sheet Download Page 3

Siemens Industry, Inc. 5300 Triangle Parkway, Norcross, GA 30092      

A5E31166447A-002

Auxiliary Contact

A  maximum  of  two  auxiliary  units  can  be  installed  in  the  re

-

cesses of each contactor (see Fig. 5 for location and bottom of 

Table 4 for the auxiliary units catalog numbers and their contact 

configuration). Auxiliary  units  mount  by  means  of  spring  clip 

and retainer screw. To remove the unit rotate the retainer screw 

several times (counter-clockwise) and then slide the auxiliary 

contact unit out of the recess.

Fig. 2  Connection Diagram for Common/Separate Control  

 

with Momentary Pushbutton or ON-OFF Selector  

 Switch

Table 3 - Coil

Voltage 

VAC

Freq. 

Hz

Part Number

2-4 Pole                 5 Pole

24

60 Hz

CLMC4C024

CLMC5C024

110/120

50/60 Hz

CLMC4C120

CLMC5C120

208

60 Hz

CLMC4C208

CLMC5C208

220/240

50/60 Hz

CLMC4C240

CLMC5C240

277

60 Hz

CLMC4C277

CLMC5C277

440/480

50/60 Hz

CLMC4C480

CLMC5C480

550/600

50/60 Hz

CLMC4C600

CLMC5C600

CAUTION - 

All control wiring for contactor operation must only be made to 

the coil isolation contact terminals #2, #3 and L2 terminal con-

nection points. Wiring made to any other terminal points will 

burn out the coil and diode. If a coil burnout occurs, both the 

coil and the diode must be replaced.

Coil Replacement

 –

 refer to Figure 1, Table 3.

Loosen the two screws at each side of the upper base and re

-

move the wire connections. Loosen the assembly screws (1).  

Pull the loosened upper base structure (2) forward. Unplug 

the coil (3) from the upper base, plug in a new coil and re

-

place the upper base structure while depressing the kick-out 

springs (4) to ensure they set in the molded seats in the cross-

bar (5). Reconnect  the four coil leads. Tighten the assembly 

screws referring to Table 2. Mechanically operate the unit to 

ensure there is no binding of the crossbar.

Contact Inspection

 –

 refer to Figure 1

Loosen the two arc chute screws (6) located immediately 

above and below the nameplate and remove the arc chute 

(7). The contacts (8) are visible. Re-tighten the screws per 

Table 2.

Contact Wear and Replacement –

  refer  to  Figure  1, 

Table 4.

     CAUTION: Install arcbox prior to energization

Contacts are designed for a long service life based on a spe

-

cific  electrical  load  under  normal  service  and  environmental 

conditions. If any one of these factors is altered, a shorter ser

-

vice life or a breakdown will result. Contactors are subject to 

both mechanical and electrical wear during their operation. In 

most cases mechanical wear is insignificant. The erosion of 

the contacts is due to electrical wear. During arcing, material 

from each contact is vaporized and blown away from the useful 

contacting surface.

Note:

 When contact replacement is required, it is necessary 

to replace both stationary and moving contacts plus moving 

contact overtravel springs. After replacement, manually oper-

ate switch to be sure binding does not occur.

After removing the arc chute (7) and with replacement contacts 

in hand, compress the overtravel spring (9) and remove the 

moving contact (8) from the crossbar (5). Remove any power 

connections.  Remove  screws  (10)  and  lift  out  the  stationary 

contact carriers (11). The new contacts are then installed by 

reversing the above procedure and referencing Table 2 for

torque specifications. Moving contacts should be free to move, 

overtravel spring seated, and the crossbar free to move when 

the arc chute is in position. Silver cadmium oxide contact but-

tons require NO dressing or lubrication during their life.

Magnet - Armature Assembly

Self alignment and permanent air gap features of the magnet 

armature make replacement unnecessary. Mating pole face 

surfaces should be kept clean.

OFF

ON

OFF

ON

VOLTAGE

CONTROL

(L1)

1

(L2)

X2

ON

OFF

( + )

( - )

BLACK

( + )

( - )

AC

AC

L2

RED

WHITE

CLMFCCK11

3

2

RE

D

CLMFCAK11

OFF

ON

RE

D

CLM CONTACTOR

All manuals and user guides at all-guides.com

Summary of Contents for CLM0C

Page 1: ...loads Each contactor and its associated load should be protected against short circuits by a suitable branch circuit pro tective device selected in accordance with the National Electric Code NEC Description AC Coil Data Poles Inrush VA Dropout VA 2 4 410 40 5 410 40 Care should be taken when servicing that leads do not be come changed from their factory installed terminals or im proper operation a...

Page 2: ... de energized With power off operate contactors relays and interlocks to see that they work freely See that all terminals and current carrying connections are clean and tight For electrical connection wire per one of the schematics shown in Fig 2 thru 4 depending on the desired control Magnetically latched contactors are equipped with coils designed for intermittent duty only Faulty coil action ca...

Page 3: ...nspection refer to Figure 1 Loosen the two arc chute screws 6 located immediately above and below the nameplate and remove the arc chute 7 The contacts 8 are visible Re tighten the screws per Table 2 Contact Wear and Replacement refer to Figure 1 Table 4 CAUTION Install arcbox prior to energization Contacts are designed for a long service life based on a spe cific electrical load under normal serv...

Page 4: ...ig 5 Dimension Drawing 30 Amp Device VOLTAGE CONTROL L1 L2 ON OFF BLACK AC AC L2 RED WHITE CLMFCCK11 3 2 RED CLMFCAK11 OFF ON RED CR REMOTE DEVICE CR CR CLM CONTACTOR VOLTAGE CONTROL ON OFF BLACK AC AC L2 RED WHITE CLMFCCK11 3 2 RED ON OFF RED CR REMOTE CR CR L1 1 L2 X2 H A O DEVICE SELECTOR SWITCH CLM CONTACTOR All manuals and user guides at all guides com ...

Page 5: ...against dust moisture and falling objects Apparatus stored for long periods may corrode Damage while stored will be minimized by maintaining the best possible storage conditions and by periodically inspect ing the equipment and arresting the progress of corro sion and other forms of deterioration which may be found A small amount of heat will stop corrosion that occurs from moisture due to condens...

Page 6: ...sed to energize and close the contactor and for the release circuit It is designed for short time actuation of 1 3 cycles only All coils are designed with a small wattage resistor in addition to a diode at coil voltage higher than 120 Volts Remote solid state switching devices have off state leakage currents They may also pass utility transient voltages through to the device electronics The low le...

Reviews: