background image

Installation Sheet

January, 2016

Supersedes February, 2013

s

E87010-A0104-T003-A6-CLM0

Lighting and Heating Contactor

              30 Amp 2, 3, 4, 5 Pole

                Magnetically Latched

A5E31166447A-002

Siemens Industry, Inc. 5300 Triangle Parkway, Norcross, GA 30092     

Table 1 – Contactor Ratings

Contactor Rating

Catalog Number

CLM0C

Cont. Current Rating, Amp.

30

Tungsten

Max. Volts, line-line

480

Max. Volts, line-Neutral

277

Ballast

Max. Volts, line-line

600

Max. Volts, line-Neutral

346

Heating

Max. Volts, line-line

600

Max. Volts, line-Neutral

346

Auxiliary Contact Ratings (A600, R300)

Voltage

Continuous

Make

Break

120-600 VAC

10A

7200VA

720VA

72-120 VAC

10A

60A

720VA

28-72 VAC

10A

60A

10A

28-300 VDC

1A

28VA

28VA

Theory of Operation

Each contactor contains a permanent magnet built into its struc-

ture that will maintain the contactor in its energized state indefi

-

nitely without using control power. When energized, DC voltage 

is applied to produce a magnetic field that reinforces the polarity 

of the permanent magnet and the contactor closes. Immediately, 

the current to the coil is disconnected by the coil clearing aux-

iliary contact. In order to open the contactor, it is necessary to 

create a field through the OFF coil in the reverse direction to the 

permanent magnet. This momentarily cancels the magnetic at-

traction and the contactor drops out.

Magnetically latched CLM lighting and heating contactors can 

control tungsten, fluorescent and metal vapor lamp or heating 

loads. (Table 1 below shows the voltage and current rating for 

various loads). Each contactor and its associated load should be 

protected against short circuits by a suitable branch circuit pro-

tective device selected in accordance with the National Electric 

Code (NEC).

Description

  

AC Coil Data

Poles

Inrush VA

Dropout VA

2-4

410

40

5.

410

40

Care should be taken when servicing that leads do not be-

come changed from their factory installed terminals, or im

-

proper operation and possibly permanent damage to the 

contactor could result.

CAUTION: Do not apply AC voltage directly to the coil 

terminals of this device! The permanent magnet will be 

demagnetized and the rectifier will be damaged if alter

-

nating current or wrong polarity direct current is ap-

plied directly to the coil.

Each CLM contactor has an electronic control module 

“CLMKCMR” which is used to energize and close the 

contactor and for the release circuit. It is designed for short 

time actuation of 1-3 cycles only. All coils are designed with 

a small wattage resistor in addition to a diode at coil voltages 

higher than 120 volts. Remote solid state switching devices 

have ‘off state’ leakage currents. They may also pass utility 

transient voltages through to the device electronics. The low  

level ‘off state’ voltages are insufficient to actuate the contactor 

but large enough to burn out the resistors. Normal actuating 

voltages are quickly disconnected from the coils and control 

module by the latch clearing contacts. Coil and module 

failures are possible when used with solid state relays and 

PLC outputs. 24-volt systems are ok to use, but 120 volts 

and above should be discouraged. If higher voltages cannot 

be avoided, an interposing relay should be used.

All manuals and user guides at all-guides.com

all-guides.com

Summary of Contents for CLM0C

Page 1: ...loads Each contactor and its associated load should be protected against short circuits by a suitable branch circuit pro tective device selected in accordance with the National Electric Code NEC Description AC Coil Data Poles Inrush VA Dropout VA 2 4 410 40 5 410 40 Care should be taken when servicing that leads do not be come changed from their factory installed terminals or im proper operation a...

Page 2: ... de energized With power off operate contactors relays and interlocks to see that they work freely See that all terminals and current carrying connections are clean and tight For electrical connection wire per one of the schematics shown in Fig 2 thru 4 depending on the desired control Magnetically latched contactors are equipped with coils designed for intermittent duty only Faulty coil action ca...

Page 3: ...nspection refer to Figure 1 Loosen the two arc chute screws 6 located immediately above and below the nameplate and remove the arc chute 7 The contacts 8 are visible Re tighten the screws per Table 2 Contact Wear and Replacement refer to Figure 1 Table 4 CAUTION Install arcbox prior to energization Contacts are designed for a long service life based on a spe cific electrical load under normal serv...

Page 4: ...ig 5 Dimension Drawing 30 Amp Device VOLTAGE CONTROL L1 L2 ON OFF BLACK AC AC L2 RED WHITE CLMFCCK11 3 2 RED CLMFCAK11 OFF ON RED CR REMOTE DEVICE CR CR CLM CONTACTOR VOLTAGE CONTROL ON OFF BLACK AC AC L2 RED WHITE CLMFCCK11 3 2 RED ON OFF RED CR REMOTE CR CR L1 1 L2 X2 H A O DEVICE SELECTOR SWITCH CLM CONTACTOR All manuals and user guides at all guides com ...

Page 5: ...against dust moisture and falling objects Apparatus stored for long periods may corrode Damage while stored will be minimized by maintaining the best possible storage conditions and by periodically inspect ing the equipment and arresting the progress of corro sion and other forms of deterioration which may be found A small amount of heat will stop corrosion that occurs from moisture due to condens...

Page 6: ...sed to energize and close the contactor and for the release circuit It is designed for short time actuation of 1 3 cycles only All coils are designed with a small wattage resistor in addition to a diode at coil voltage higher than 120 Volts Remote solid state switching devices have off state leakage currents They may also pass utility transient voltages through to the device electronics The low le...

Reviews: