Wiring
Use only class 2 rated power source with proper current limiting.
● Use only class 2 rated power source with proper current limiting.
● Disconnect power supply before beginning wiring, or making wiring connections, to
prevent electrical shock or equipment damage.
Commissioning
Commissioning configures I/Os and tests the damper operation and any configured outputs.
It can only be done using the Climatix Mobile application or under Configuration State from
the controller. The three LEDs blink yellow if the controller enters Configuration State.
To Commission under the controller’s Configuration State
a) From the default HMI screen, press Enter + Up.
The '5CONFIG STATE' screen displays.
b) Press Enter, and then confirm the switch by pressing Enter again.
c) Configure I/Os and/or test connected devices.
d) If configurations are done, press Enter + Up or Down to switch to the '8RUN STATE'
screen, then press Enter twice to go back to Running State.
The '1FREECOOL' screen displays.
Commissioning is also possible from the mobile application. See
Don't interrupt damper test once it starts.
Operation
Customers can download the mobile application by scanning the Mobile APP QR code on
the device and perform operations on their smartphones or tablets or directly on the device.
When performing operations from the mobile application, ensure that a WLAN stick is
plugged into the USB port and connection between the smartphone/tablet and the WLAN
network is established.
Operations that can be performed from the local device are as follows:
● Change basic settings like the following:
– Temperature shutoff setpoint
– Enthalpy shutoff setpoint if an RH input is detected
– Mixed-air temperature modulating setpoint
– The ppm value for DCV (Demand Control Ventilation)
– Damper minimum position
– Temperature unit
– Fan airflow or CFM value
– ERV (Energy Recovery Ventilation) outside air temperature setpoint if 'ERV' is
selected for AUX1-O or AUX2-O
– Exhaust fan startup setpoint if exhaust fan is chosen
– Etc.
● Change advanced settings like the following:
– Damper position anti-freeze protection settings
– Damper position during shutdown
– Highest stage cooling delay time
– Min. and max. leaving air temperature