PROGRAMMING
The Silent Knight Model 5230 LCD Keypad Programmer can be connected temporarily to Pin
P4 on the Silent Knight 5128 Main Board (See Figure 27) for on-site programming or trouble-
shooting of the communicator. English language messages assist in entering data, changing
the 24-hour test time, and describing conditions currently in effect.
Table 15 lists the recommended program for the Silent Knight 5128/5129 Digital Fire Commu-
nicator. Before you begin programming, read the
Step Programming Form
in the
Silent
Knight Model 5128/5129 Fire Slave Communicator Installation Manual,
August, 1994, P/N
150805, provided with the Silent Knight 5128/5129.
NOTES:
1. If the selection is left blank, the user must fill in the proper information.
2. Skip = No selection is required.
3. After each selection is made, press the ENTER key to proceed to the next step.
4. a.
If the Silent Knight Model 5129 Digital Fire Communicator is used and independant
AC Fail is to be reported,
enter a number from 6 to 15 hours; otherwise, enter 0.
Six hours is required for Central Station; 15 hours is required for Remote Sation.
b.
If the Silent Knight Model 5128 Digital Fire Communicator is used,
enter 0 hours.
5. The PXL
must be programmed
to delay the trouble relay on AC fail. Follow the steps
below:
a. Enter the Program mode.
b. From the Set Timers menu, select
Set AC Fail Relay Delay
to 6 hours for Central
Station applications or 15 hours for Remote Station applications.
No.
Option Name
Select
1
ZONE ACTIVE
0
2
ZONE SUPERVISED
yes
3ALARM CHANNEL INPUT
0
4
TROUBLE CHANNEL INPUT 0
5
SUPERVISORY CHANNEL
0
6
ZONE RESPONSE 1
0
7
ZONE RESPONSE 2
SKIP
See Note 2
8
ZONE RESPONSE 30
9
ZONE RESPONSE 4
0
10
RELAY 1
1
11
INSTALLERS CODE
12
OPERATORS CODE
13DIALER TYPE
0
14
COMPUTER ENABLE
yes
15
TOUCHTONE LINE 1
yes
16
TOUCHTONE LINE 2
yes
17
MUST REPORT 1
yes
18
MUST REPORT 2
yes
19
AC MONITORING
2
20
AC LOSS HOURS
See Note 4
No.
Option Name
Select
Step
21
RINGS
SKIP
See Note 2
22
3/1 ALARM CODE
233
/1 TROUBLE CODE
24
3/1 RESTORE CODE
25
3/1 TEST CODE
26
ALARM 1 FIRST
yes
27
TROUBLE 1 FIRST
yes
28
TEST 1 FIRST
yes
29
ACCOUNT 1
30
ATTEMPTS 1
3
31
FORMAT 1
32
PHONE 1
33
ACCOUNT 2
34
ATTEMPTS 2
3
35
FORMAT 2
36
PHONE 2
37
COMPUTER ACCOUNT
SKIP
See Note 2
38
COMPUTER PHONE
SKIP
See Note 2
39
TEST TIME
40
CURRENT TIME
Step
Table 15
Silent Knight Model 5128/5129 Programming Table