9
Building Technologies
A6V10202198_m_en_--
Fire Safety
2018-06-15
Technical data
OH720
OP720
HI720 / HI722
Operating voltage
DC 12…33 V
DC 12…33 V
DC 12…33 V
Operating current (quiescent)
~230 µA
~220 µA
~200 µA
Max. number of external alarm
indicators that can be connected
2
2
2
Operating temperature
-10...+55 °C
-10...+55 °C
-10...+55 °C
Storage temperature
-30...+70 °C
-30...+70 °C
-30...+70 °C
Air humidity (short-term moisture
condensation permitted)
95 % rel.
95 % rel.
95 % rel.
Communication protocol
C-NET
C-NET
C-NET
Color
~RAL 9010 pure white ~RAL 9010 pure white ~RAL 9010 pure white
Weight
0.144 kg
0.138 kg
0.130 kg
Protection category (IEC 60529)
IP40
IP40
IP40
Protection category (IEC 60529)
with detector base seal RS720
IP42
IP42
IP42
Standards
CEA4021, EN 54-7,
EN 54-17
EN 54-7, EN 54-17
EN 54-5, EN 54-17
Approvals
VdS
LPCB
FM
DNV GL (marine)
G209064
531d/01
3038424
MEDB00003UK
G209068
531e/01
3038424
MEDB00003UK
G209065 / G209146
531f/01 / 531f/02
3037921
MEDB00003UR
Permissible wind speed
Max. 5 m/s
Max. 5 m/s
-
C-NET system compatibility
FS720, FC360
FS720, FC360
FS720, FC360