![Siemens Cerberus PRO FS720 Components/Spare Parts/Repair Parts Download Page 14](http://html.mh-extra.com/html/siemens/cerberus-pro-fs720/cerberus-pro-fs720_components-spare-parts-repair-parts_379139014.webp)
Networkable fire control panels
14
Building Technologies
A6V10227652_i_en_--
Fire Safety
2016-05-30
3.3
Fire control panels FC724 (4-loop) in housing (Comfort)
FC724-ZA
Fire control panels (4L)
Part no.
S54400-C30-A2
FC724-ZE
Fire control panels (4L, 2LED)
Part no.
S54400-C30-A3
FC724-ZA
FC724-ZE
With 48 indicator groups, with
each one red and yellow LED
Expansion
see chapter 0
Accessories
see chapter 3.6
Product data sheet A6V10207176
–
The FC724 is a compact, prefabricated fire control panel with integrated operating unit capable of
processing FD720 device signals.
–
The fire control panel may be used as a stand-alone unit or networked.
–
Up to 32 fire control panels and fire terminals can be connected in a single cluster
(C-WEB/SAFEDLINK network), or up to 16 panels when the cluster is connected to a danger
management system. Using a fiber-optic backbone (C-WEB/LAN) up to 14 of these clusters with up
to 16 panels each can be networked. This topology enables the construction of an EN 54-compliant
network with up to 64 fire control panels and fire terminals.
–
The FXS7212 Cerberus-Engineering-Tool permits the system to be adapted to specific customers'
requirements.
–
Connection of Siemens Danger Management System.
–
Ideally suited for large-size applications, e.g. industrial facilities, regional banks, office complexes,
etc. The FC724 can be used by the flexible cross-linking possibilities however also for extensive
systems.
Consists of:
–
Housing (Comfort)
–
Operating unit
–
Periphery board
–
Power supply 150 W, emergency power supply (batteries must be ordered separately)
Technical data
Mains voltage
AC 230 V
Power supply
150 W
Operating voltage
DC 21…28.4 V
Operating current
Max. 5 A
Battery capacity
2 x 12 V, 7…26 Ah
Connectable detector series
Cerberus PRO FD720 (C-NET)
Number of lines
4 (8) loops or 8 (16) stub lines
Number of addresses
Max. 504
Relay output
–
RT alarm
–
RT fault
1
1
Monitored outputs
–
Alarm
–
Fault
–
Horn
1
1
2
Free programmable inputs/outputs
12
Operating temperature
-8…+42 °C
Storage temperature
-20…+60 °C
Humidity (no condensation permitted)
≤95 % rel.
Dimensions (W x H x D)
–
Without cover cap
–
With cover cap
430 x 796 x 160 mm
430 x 796 x 188 mm
Color
–
Housing
grey, ~RAL 7035
–
Cover
grey, ~RAL-Design 050 00 00
Protection category
IP30
Approvals VdS / LPCB
G209077 / 126bn/07