Connect external components
Desk call station PT2001-A1
7
126 | 173
A6V10430579_en--_b
7.1.3 Connect DC 24 V power supply
The DC 24 V power supply connection is used to supply the PT2001-A1 with
power.
DC 24 V power connector - 'CN2'
Pin
Description
Remark
1
DC 0 V
2
DC 24 V
Table 96: PT2001-A1 DC 24 V power connector - 'CN2'
The DC 0 V is galvanically isolated from the reference voltage (GND), analog audio
and all digital interfaces. The galvanic isolation prevents earth loops and earth
bypasses.
The 24 V can be supplied from a cabinet or an external power supply 'Merawex
ZSP135 DR-7A-3 40 Ah' PP2004-A1 with a separate cable.
7.1.3.1 Power supply from a cabinet
Fig. 87: PT2001-A1 power supply from a cabinet
1 Cerberus PACE cabinet
2 External 'Desk call station (19 buttons)' PT2001-A1 with accessories
3 DC/DC converter 'MeanWell SD-50B-24 DC/DC Converter (50W)' PCA2011-
A1 or 'MeanWell SD-100B-24 DC/DC Converter (100W)' PCA2018-A1
4 'Ground fault monitoring (24V)' PCA2001-A1
5 Fuse 1 A
7 DC 24 V wiring to 'Desk call station (19 buttons)' PT2001-A1 or other
components
PT2001
(PT2002)
DC/DC
PCA2011
PCA2018
Ground Fault
PCA2001
Fuse
(PT2001)
PT2002
Fuse
DC 24 V
DC 24 V
DC 24 V
Cabinet
1
1
1
2
1
3
1
4
1
5
1
7
1
2
1
5
1
7
Fuse
DC 24 V
1
5
1
7
Other
devices