![Siemens Cerberus NW8005 Technical Manual Download Page 21](http://html.mh-extra.com/html/siemens/cerberus-nw8005/cerberus-nw8005_technical-manual_384230021.webp)
17
Siemens Building Technologies
Cerberus Division
e3180a.doc
12.2000
5.3.4
Assessment of lower quality cable
If during an
Auto Test
the cable is assessed as bad (display FAIL Near or FAIL Far), it
must not be used for a maximum length data bus. This cable must only be used for a
reduced cable length. The maximum permissible lengths can be worked out with di-
minished thresholds (templates).
Example for LON and C-Bus
Templates for
CerCom/LON
Templates for
CBUS
Assessment
LONV1_Q1
CBUSV1_Q1
no reduction of maximum length
LONV1_Q2
CBUSV1_Q2
reduction of maximum length by 15%
LONV1_Q3
CBUSV1_Q3
reduction of maximum length by 30%
LONV1_Q4
CBUSV1_Q4
reduction of maximum length by 50%
Q1 ... Q4 not complied with
-----
reduction of max. length to 500m
equivalent to free bus topology
-----
Q1 ... Q4 not complied with
Cable cannot be used
Measures to be taken in the event of an error
LED-LCD display
Comment
Measures
Fail Near
lights red
Fail Far
lights red
LED
Meas. function lights red
With one measuring function a
threshold was exceeded at the
near and/or far end
-
Repeat measurement with
diminished threshold
-
Check cable sections individu-
ally
Remote not found
The Master does not recognize the
partner device
-
Check continuity
-
Pair detection
-
Check cable sections individu-
ally
For measurement see section
5.3.5
LCD
--------
No results are available
5.3.5
Check cable continuity
The function
Pair Detect
simplifies the location of a wire pair in a bundle of cables.
1.
On the transmission side generate a signal tone with the
Pair Detect
key
➜
LED
Tone TX
lights up green
2.
On the receiver side generate a signal tone with the
Pair Detect
key
➜
LED
Tone RX
lights up green
➜
If continuity is positive a signal tone is sounded