Siemens Building Technologies Group

04.2002

3.1

Programming switches, jumpers

Battery type: S2

To set temperature compensation according to information from the various battery
manufacturers.

Possible battery variants

Programming switch S2

Var.

Battery manufacturer

Battery model

S2-1

S2-2

S2-3

S2-4

0

off

off

off

off

1

on

off

off

off

2

Varta

Shin-Kobe (Hitachi)

Kobe PSD (Power Storage
Germany)

CF 12-24 (VM 1224)

HP..-12

HP..-12

off

on

off

off

3

Genesis

G12V120W15

on

on

off

off

4

Sunrise

Panasonic

LCL 12V24S

LCL 12V..P

off

off

on

off

5

Phoenix (Korea)

FNC 12..0

on

off

on

off

6

Yuasa

NP..-12B

off

on

on

off

7

Sonnenschein Dryfit

A212/..G5

on

on

on

off

8

Power-Sonic

PS12..0

off

off

off

on

9

Hagen Drysafe

HDS-12..0NB

on

off

off

on

10

Sonnenschein Dryfit

A512/..G5

off

on

off

on

11

ALARMCOM (FIAMM) 

1)

FG...

on

on

off

on

12

off

off

on

on

13

on

off

on

on

14

off

on

on

on

15

on

on

on

on

”S2” is set to variant 11 (ALARMCOM) at the factory

1)

 available from index ’AA’ onwards

Monitoring signals: S3

For settings refer to the „Application examples”, chapter 4

Operating mode: R66, R67

Operating mode:

R66

R67

a) Battery operation and  symmetry monitoring

b) Battery operation without  symmetry monitoring

c) Operation with external voltage (instead of battery)

d) Operation without battery or external voltage

Door contact simulation: X2

Without door contact: insert jumper X2 at first E3C021.

Factory settings 

without jumper ex factory 

Summary of Contents for Cerberus MN7002

Page 1: ...Cerberus MN7002 Power supply Description Fire Security Products Siemens Building Technologies Group ...

Page 2: ...thereof in full or in part nor to make them available to any third party without our prior express written authorization nor to use it for any purpose other than for which it was delivered to him Nous nous réservons tous les droits sur ce document ainsi que sur l objet y figurant La partie recevant ce document reconnaît ces droits et elle s engage à ne pas le rendre accessible à des tiers même par...

Page 3: ...ge in function of temperature 7 3 4 Connections of E3C021 8 4 Application examples 9 4 1 Conventional power supply 9 4 2 Extended emergency power capacity 10 4 3 Power splitting 11 5 Mounting possibilities 12 5 1 In danger management system DMS7000 12 5 2 On L section plate of the Z1B050 mounting set 12 5 3 In CZ10 fire detection system control unit 13 5 4 In CC60 gas warning system control unit 1...

Page 4: ...II Fire Security Products Siemens Building Technologies Group 04 2002 ...

Page 5: ...arging current up to 1 7A selectable charging caracteristics depending on battery model symmetry monitoring automatic battery load test temperature compensation for battery charging voltage via external temperature sen sor a Battery operation and symmetry monitoring b Battery operation without symmetry monitoring c Operation with external voltage instead of battery d Operation without battery or e...

Page 6: ...set short PTC with 0 8m cable battery cables blue red green 0 8m connection cable B2F020 E3C021 blue red 0 3m connection cable E3C021 control unit 0 8m with AMP T connector earth wire 0 5m Z3I850 496588 Cable set long PTC with 2 5m cable battery cables blue red green 2 2m connection cable B2F020 E3C021 blue red 0 3m connection cable E3C021 control unit 2 0m with AMP T connector earth wire 0 5m pro...

Page 7: ...ption 40 220VA Mains fuse 3 15A slow blow can only be changed at factory Output current up to 6A continuous Output voltage 29 6VDC 2 Residual ripple max 300mVpp Quiescent current on battery operation 0mA Temperature fuse automatic switch off at 90 C Cooling no special cooling required Temperature range 0 55 C Standard prEN54 4 Dimensions 120 100 x 42 x 204mm Wire range max 4mm2 Connections of B2F0...

Page 8: ...t inserted ex works Key data E3C021 Input voltage 29 6VDC 2 from B2F020 module Charging section Battery 2 x 12V 6 40Ah lead battery Charging characteristics Can be adjusted to different makes of battery using pro gramming switch S2 Charging current up to 1 7A current limitation Temperature compensation of battery charging voltage with external temperature sensor Battery monitoring battery presence...

Page 9: ...12B off on on off 7 Sonnenschein Dryfit A212 G5 on on on off 8 Power Sonic PS12 0 off off off on 9 Hagen Drysafe HDS 12 0NB on off off on 10 Sonnenschein Dryfit A512 G5 off on off on 11 ALARMCOM FIAMM 1 FG on on off on 12 off off on on 13 on off on on 14 off on on on 15 on on on on S2 is set to variant 11 ALARMCOM at the factory 1 available from index AA onwards Monitoring signals S3 For settings ...

Page 10: ...0V converter malfunction Battery voltage 29 5V or 25V charging module malfunction Battery charging module malfunction Temperature sensor open line short circuit Temperature sensor measures 55 C EEPROM check sum error LED Power on Input voltage 28 5V LED Trouble battery Battery voltage 23V Open line to battery or fuse F11 F13 blown Autom test to indicate battery presence negative Autom battery load...

Page 11: ...2 26 2 28 2 30 2 32 2 34 2 36 2 38 2 40 2 42 2 44 2 46 2 48 2 50 0 10 20 30 40 50 V Z T C Var 3 Genesis G12V120W15 Ua min V Ua max V Ua min V Ua max V Ua middle V 2 10 2 12 2 14 2 16 2 18 2 20 2 22 2 24 2 26 2 28 2 30 2 32 2 34 2 36 2 38 2 40 2 42 2 44 2 46 2 48 2 50 0 10 20 30 40 50 V Z T C Var 4 Sunrise LCL 12V24S Panasonic LCL12V24P Ua min V Ua max V 2 10 2 12 2 14 2 16 2 18 2 20 2 22 2 24 2 26...

Page 12: ...P T connector 24VDC load 1 2A 24VDC load 2 2A 24VDC load 3 2A F12 6 3A F13 6 3A F11 6 3A X1 Door contact or jumper X2 at first E3C021 only Common for monitoring signals or S3 1 on 1 2 3 4 5 6 Emerg power Power supply 24V Battery Door switch Parallel connection next E3C021 Monitoring signals to control unit brown yellow white green Monitoring signals from next E3C021 K3 Z3B220 cable or S3 2 on at l...

Page 13: ...ergency power capacity 40Ah 4 3A for all load circuits 1 7A for batteries ü Mains feeder via back up fuse of max 10A E3C021 Load 1 2A Load 2 2A Load 3 2A Control unit PTC 12V 12V 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 K3 K4 Control unit Batteries 40Ah X1 X2 S3 1 S3 2 ON ON 115VAC 230VAC 10A 6A B2F020 refer to page 8 1 7A 4 3A ...

Page 14: ... 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 E3C021 Load 1 2A Load 2 2A Load 3 2A Control unit PTC 12V 12V 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 E3C021 Load 1 2A Load 2 2A Load 3 2A PTC 12V 12V 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 K3 K4 K3 K4 K3 K4 first E3C021 last E3C021 Common Control unit Common Batteries 40Ah Z3B220 Z3B220 Batteries 40Ah Batteries 40Ah X1 X2 S3 1 S3 2 X1 X2 S3...

Page 15: ... 8 9 10 11 12 13 14 15 16 17 18 E3C021 Load 1 2A Load 2 2A Load 3 2A PTC 12V 12V 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 K3 K4 K3 K4 K3 K4 last E3C021 Common supply Common supply Batt 40Ah Z3B220 Z3B220 Batt 40Ah X1 X2 S3 1 S3 2 X1 X2 S3 1 S3 2 X1 X2 S3 1 S3 2 OFF ON OFF ON ON E3C021 Load 1 2A Load 2 2A Load 3 2A Control unit PTC 12V 12V 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 K3 K4 first ...

Page 16: ... Technologies Group 04 2002 5 Mounting possibilities 5 1 In danger management system DMS7000 R1P061 power supply rack delivered as complete wired unit without batteries 5 2 On L section plate of the Z1B050 mounting set 120 210 B2F020 E3C021 Z1B050 130 ...

Page 17: ...e1493d 13 Fire Security Products Siemens Building Technologies Group 04 2002 5 3 In CZ10 fire detection system control unit 5 3 1 On G1E010 universal bracket ...

Page 18: ...C021 Z1B050 Mounting of two MN7002 in series G housing 1 2 3 Z3I030 1 2 3 4 4 6 Z3I050 G3E010 11 12 13 14 15 16 17 18 19 31 32 33 34 AX1201 AX1201 AX1201 AX1201 mount the second MN7002 on Z3I050 Z3I030 can also be used in place of Z3I050 position one paire of batteries on YAH00 s the other is positioned on the base of the control unit housing 2x YAH00 Z3I 5 B2F020 E3C021 Z1B050 B2F020 E3C021 Z1B05...

Page 19: ...G3E010 11 12 13 14 15 16 17 18 19 31 32 33 34 Z3I AX1201 AX1201 B2F020 E3C021 Z1B050 1 2 G1E010 Z3I140 B2F020 E3C021 Z1B050 G3E010 11 12 13 14 15 16 17 18 19 31 32 33 34 Z3I AX1201 AX1201 35 36 37 38 39 5 5 In CZ1 02 extinguishing system control unit G2E020 Z3I AX1201 AX1201 12 G1E010 Z3I110 B2F020 E3C021 Z1B050 22 21 12 ...

Page 20: ...iemens Building Technologies Group 04 2002 Document no Edition e1493d 04 2002 Siemens Building Technologies AG CHC8708 Männedorf Alte Landstrasse 411 Tel Fax www cerberus ch 41 1 922 61 11 41 1 922 64 50 MN7000 2 CG60 4 Manual Section ...

Reviews: