HARDWARE INSTALLATION
E1110A.DOC
Data and design subject to change without notice. Supply subject to availability
© Copyright by CERBERUS AG, CH-8708 Männedorf, Switzerland 1995
01.96
39[51]
10 Hardware installation
10.1 Power requirements and connections
To power the CMX you need a power supply with the following characteristics:
Feature
Value
Unit
Voltage min
12
V
max
28
V
Current - idle
80 @ 12 V
mA
60 @ 28 V
mA
Current - max
360 @ 12 V
mA
420 @ 28 V
mA
Table 10.1 - CMX-24I power supply data
Feature
Value
Unit
Voltage min
12
V
max
28
V
Current - idle
70 @ 12 V
mA
60 @ 28 V
mA
Current - max (no output connection)
240 @ 12 V
mA
200 @ 28 V
mA
Current - max (with 24 relay outputs activated)
550 @ 12 V
mA
470 @ 28 V
mA
Table 10.2 - CMX-24O power supply data
Feature
Value
Unit
Voltage
min
12
V
max
28
V
Current - idle
80 @ 12 V
mA
65 @ 28 V
mA
Current - (all inputs and outputs active)
320 @ 12 V
mA
360 @ 28 V
mA
Current - max (all inputs and relay outputs active)
430 @ 12 V
mA
460 @ 28 V
mA
Table 10.3 - CMX-16/8 power supply data